Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 8 – WATER HEATER MANAGEMENT

Page 122 of

206

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0078_0L

PRI: 11/25/2014

Phone: 800-526-0288

GF-128

WHM MENU

See section 8-6 for a range of choices and the default values.

ITEM

MENU LEVEL &

OPTION

DESCRIPTION

26

Valve Override

Valve Override allows the user to manually control an Isolation Valve
as follows:
Off– Valve Override is disabled and WHM will automatically control
the Isolation Valve.
Open – Valve Override is enabled and the Isolation Valve is
Opened.
Note! The valve will remain opened as long as the Valve Override
feature is set to Open. Care must be taken to insure that this mode is
turned Off during normal WHM operation.
Closed – Valve

27

Valve Feedback

Enable or disable the Valve feedback feature

28

Valve Fdbk timer

The time allotted the Valve to Open or Close once a command has
been issued before invoking a fault.

29

ValveFdbk Status

Displays a Valve status of the unit:

0= valve closed
1= valve open
2= valve stuck closed
3= valve stuck open

30

MB Head Temp En

Enable or disable the Modbus Header Temp sensor

31

WHM Header Temp

Display the Header Sensor

32

Mdbus Temp Units

Modbus temp unit format (˚F or ˚C)

33

Header Temp Addr

Modbus header Temp address.

34

Header Tmp Point

Modbus point to read the header temp register point

35

MB Outdr Sens En

Enable or disable the Modbus Outdoor Temp sensor

36

WHM Outdr Temp

Display Outdoor temp value

37

Outdoor Tmp Addr

Modbus Outdoor Temp address

38

Outdoor Tmp Pnt

Modbus point to read the Outdoor Temp register point

39

Err Threshold

Max allowable comm errors before a comm. fault is invoked.

40

Comm Address

Set the Comm Address for the unit (This option also available in setup
menu)

41

1 WHM Units 8

This menu item shows the current status for each unit controlled by
WHM (8 max.). The characters displayed are defined as:
- = Off Line, * = Not available (fault, etc.), 0 = Off, 1 = On,
A = Lead On, a = Lead Off, B = Lag On, b = Lag Off

The following example shows the status of 5 units being controlled by
WHM:
1 WHM Units 8
_ 1_ _0_ _1_ _*_ _A_ _b_ ___ ___

Where: Unit 1 & 3 = On, Unit 2 = Off, Unit 4 = Not available,
Unit 5 = Lead On, Unit 6 = Lag Off