CHAPTER 4 – INITIAL START-UP

Page 58 of

206

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0078_0L

PRI: 11/25/2014

Phone: 800-526-0288

GF-128

NATURAL GAS Combustion Calibration - Continued

Figure 4-4. Gas Pressure Adjustment Screw Location

13.

Replace the brass cap on the SSOV gas pressure adjustment if it was previously removed.

14.

With the valve position at 100%, insert the combustion analyzer probe into the 1/8” port at
the rear of the exhaust manifold. Allow enough time for the combustion analyzer to settle.

15.

Compare the oxygen (O

2

)

level, carbon monoxide (CO), nitrogen oxide (NOx) and flame

strength readings with the range

shown in step 19, below.

You may need to adjust O

2

%

above this range to meet ultra-low NOx requirements or to avoid combustion tone issues.

16.

Press the MENU key on the front panel of the C-More until Combustion Cal Menu appears
on the display.

17.

Press the ▲ arrow key until SET Valve Position reads 100%. Press the ENTER key.

18.

Press the CHANGE key and observe that CAL Voltage 100% is flashing.

19.

The oxygen level at the 100% valve position should be as shown below. Also, ensure that
the nitrogen oxide (NOx), carbon monoxide (CO) and flame strength readings match the
following values:

Combustion Calibration Readings at 100% Valve Position

Valve

Position

Oxygen (O

2

)

%

Nitrogen Oxide

(NOx)

Carbon Monoxide

(CO)

Flame µA

100%

6.0% ± 0.25%

<20 ppm

<100 ppm

> 6 µA

20.

If the oxygen level is not

within the specified range, adjust the level using the ▲ and ▼

arrow keys. This will adjust the output voltage to the blower motor as indicated on the

display. Pressing the ▲ arrow key increases the oxygen level and pressing the down ▼
arrow key decreases the oxygen level.

21.

Once the oxygen level is within the specified range at 100%, press the ENTER key to store
the selected blower output voltage for the 100% valve position. Record all readings on the
Combustion Calibration Sheets provided.

22.

Repeat steps 16 through 21 for the following valve positions (see NOTE below):

80%, 60%, 40%, 30%, 24%, 20%, 16%

NOTE

If NOx readings exceed the target values shown (<20 ppm), increase the O

2

level up to 25% higher than the listed calibration range shown in the table.
Record the increased O

2

value on the Combustion Calibration sheet.

BRASS HEX
HEAD CAP

(Remove to access gas pressure
adjustment screw)