AERCO Innovation (G-14-2265 and above) User Manual

Page 92

Advertising
background image

Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 6 – MAINTENANCE

Page 92 of

206

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0078_0L

PRI: 11/25/2014

Phone: 800-526-0288

GF-128


Figure 6-11. Air Filter Mounting Location

6.11 LOW WATER CUTOFF (LWCO) CAPACITOR INTEGRITY TEST

If the LWCO capacitor has failed, order the LWCO capacitor

Kit, P/N 69126, from AERCO,

and consult the Innovation 24 Month Maintenance Technical Instructions Document TID-0094 for
replacement instructions.

The LWCO capacitor should be tested for electrical shorts every 12 months and replaced,
then tested, every 24 months. The LWCO capacitor integrity test consists of two parts as
described in the next two sections. The first procedure explains how to test for electrical
shorting of the LWCO probe capacitor, while the second procedure instructs how to perform
the standard Low Water Cutoff test using the C-More controls.

On the Innovation series, the LWCO probe is located on the heat exchanger body on the left side
of the unit. Refer to Figure 6-12 for an illustration of the LWCO probe assembly and its
installation.

BARE HEATER – PARTIAL FRONT VIEW

AIR FILTER

FILTER CLAMP

AIR/FUEL

VALVE

BLOWER
MOTOR

Advertising