APPENDIX C – TEMPERATURE SENSOR RESISTANCE/VOLTAGE CHART

OMM-0078_0L

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 147 of

206

GF-128

Phone: 800-526-0288

PRI: 11/25/2014

APPENDIX C – TEMPERATURE SENSOR RESISTANCE/VOLTAGE

CHART

TEMPERATURE SENSOR RESISTANCE/VOLTAGE CHART

(BALCO)

TEMP (°F)

RES (OHMS)

VOLTS*

-40

-30

-20

-10

0

10

20

30

40

50

60

70

80

90

100

110

120

130

140

150

160

170

180

190

200

210

220

230

240

250

779.0

797.5

816.3

835.4

854.8

874.6

894.7

915.1

935.9

956.9

978.3

1000.0

1022.0

1044.4

1067.0

1090.0

1113.3

1137.0

1160.9

1185.2

1209.5

1234.7

1260.0

1285.6

1311.4

1337.7

1364.2

1391.0

1418.2

1445.7

1.93

1.96

1.99

2.02

2.05

2.07

2.10

2.12

2.15

2.17

2.20

2.23

2.25

2.27

2.30

2.32

2.34

2.36

2.39

2.41

2.43

2.45

2.47

2.50

2.52

2.54

2.56

2.58