APPENDIX A – INNOVATION MENU ITEM DESCRIPTIONS

Page 138 of

206

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0078_0L

PRI: 11/25/2014

Phone: 800-526-0288

GF-128

Table A-4: TUNING MENU ITEM DESCRIPTIONS

See section 3-7 for a range of choices and the default values.

MENU LEVEL & OPTION

DESCRIPTION

24

Temp Gov Enable

Enables or Disables the Temperature Governor function. The
Temperature Governor aggressively reduces the effective Fire
Rate as the Outlet Temperature approaches the High
Temperature Limit.

25

GOV Limit-5

When the Outlet Temperature exceeds the HIGH
TEMPERATURE LIMIT -5, the effective Fire Rate will be
reduced by the value entered in “GOV Limit -5”

26

GOV Limit-7

When the Outlet Temperature exceeds the HIGH
TEMPERATURE LIMIT -7, the effective Fire Rate will be
reduced by the value entered in “GOV Limit -7”

27

GOV Limit-10

When the Outlet Temperature exceeds the HIGH
TEMPERATURE LIMIT -10, the effective Fire Rate will be
reduced by the value entered in “GOV Limit -10”

28

GOV Limit-12

When the Outlet Temperature exceeds the HIGH
TEMPERATURE LIMIT -12, the effective Fire Rate will be
reduced by the value entered in “GOV Limit -12”

29

GOV Limit-15

When the Outlet Temperature exceeds the HIGH
TEMPERATURE LIMIT -15, the effective Fire Rate will be
reduced by the value entered in “GOV Limit -15”

30

PID Output

Calculated PID Output

31

P Output

Proportional Band Output

32

I Output

Integral Output

33

D Output

Derivative Output

34

Reset Defaults?

Allows Tuning Menu options to be reset to their Factory Default
values.

35

Value Debug

For Factory Personnel ONLY

36

Above 70 Fuel

For Factory Personnel ONLY

37

Below 70 Fuel

For Factory Personnel ONLY

NOTE: Feedback Gain (Item 8) is only displayed when Heater Tuning Display is enabled by

factory authorized personnel.