Innovation Water Heaters Installation, Operation & Maintenance Manual

APPENDIX J – COMBUSTION CALIBRATION (KOREA ONLY)

Page 200 of

206

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0078_0L

PRI: 11/25/2014

Phone: 800-526-0288

GF-128

Natural Gas Combustion Calibration – Continued

Figure J-1. Gas Pressure Adjustment Screw Location

11.

Next, decrease the valve open position to 16% using the ▼ arrow key. Verify that the gas
pressure at the inlet of the SSOV is 11.0” W.C. Readjust the inlet gas pressure if
necessary.

12. Insert the combustion analyzer probe into the 1/8” port at the rear of the exhaust manifold.

Allow enough time for the combustion analyzer to settle.

13. Verify that the oxygen (O

2

)

level is within the range

shown below

Also, ensure that the

carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values
shown.

Combustion Oxygen Level at

16% Valve Position

Oxygen %

± 0.5

Carbon

Monoxide

NOx

6.5 %

<50 ppm

<15 ppm

14. If the oxygen level is not within the required tolerance, the gas pressure on the

downstream side of the SSOV must be adjusted using the adjustment screw on the SSOV
regulator (Figure J-1). Slowly rotate the gas pressure adjustment (approximately 1/4-turn
increments). Allow the combustion analyzer to stabilize following each adjustment.
Clockwise rotation reduces the oxygen level, while counterclockwise rotation increases
the oxygen level.