Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 4 – INITIAL START-UP

OMM-0078_0L

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 55 of

206

GF-128

Phone: 800-526-0288

PRI: 11/25/2014

4.2.3 Accessing the Analyzer Probe Port

The unit contains a 1/8” NPT port at the rear of the exhaust manifold. This port is located above
the condensate drain connection as shown in Figure 4-2. Prepare the port for the combustion
analyzer probe as follows:

Accessing Analyzer Probe Port

1.

Refer to Figure 4-2 and remove the 1/8” NPT plug from the rear of the exhaust manifold.

2.

If necessary, adjust the stop on the combustion analyzer probe so it will extend mid-way
into the flue gas flow. DO NOT install the probe at this time


Figure 4-2. Analyzer Probe Hole Location

IMPORTANT

For Innovation Water Heater installations in Korea, refer to the Natural Gas
Combustion Calibration procedures in Appendix J.

4.2.4 Connecting Multimeter to Flame Detector

During Combustion Calibration, the flame strength generated by the flame detector is measured
using a multimeter set to the µA scale. The flame detector is mounted on the flange of the blower
side intake manifold as shown in Figure 4-3.

Proceed as follows to set up the multimeter to measure the flame strength current:

EXHAUST

MANIFOLD

VENT PROBE
PORT WITH
1/8” NPT PLUG

CONDENSATE
DRAIN