Innovation Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 6 – MAINTENANCE

OMM-0078_0L

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 93 of

206

GF-128

Phone: 800-526-0288

PRI: 11/25/2014

Figure 6-12: LWCO Probe Location (INN 1350 Shown)

6.11.1 Low Water Cutoff (LWCO) - Capacitor Electrical Short Test

This test determines if there is an electrical short between the LWCO capacitor and the heat
exchanger. Perform the capacitor electrical short test as described below.

LWCO Capacitor Electrical Short Test

1. Turn OFF AC power to the unit.

WARNING!

High voltages are used to power these units and so it is required
that power applied to these units is removed first before performing
the procedure described in this instruction. Serious personal injury
or death may occur if this warning is not observed.

LWCO Probe

Capacitor Assembly
(Covered By Large
Shrink Tubing)

Connector
(to Shell Harness)

Plastic Acorn Nut

LWCO

Probe

Terminal

PARTIAL LEFT SIDE VIEW