EVCO EVCSR338J9 User Manual
Page 26

EVCO S.p.A.
Vcolor 338 S | Installer manual ver. 1.2 | Code 144VC338SE124
page 26 of 50
10
“SPECIAL CYCLES” FUNCTION
10.1
Preliminary notes
The “Special cycles” function allows to use the work cycles
made available by EVCO.
One of the following work cycles can be started:
-
core regeneration cycle (only if the needle probe is
enabled, i.e. if parameter P2 is set at 1)
-
timed regeneration cycle
-
timed proving cycle
-
environment cooling cycle.
The following table illustrates the factory settings of the core
regeneration cycle.
SETTING
DEFAULT
MINIMUM...
MAXIMUM
work set-point
110 °C
20... 180 °C
humidification
70 %
40... 100 %
core set-point
70 °C
20... 100 °C
fan speed
minimum
vent opening
on conclusion of the cycle
The following table illustrates the factory settings of the timed
regeneration cycle.
SETTING
DEFAULT
MINIMUM...
MAXIMUM
work set-point
110 °C
20... 180 °C
humidification
70 %
40... 100 %
duration of the
phase
25 min
1... 90 min
fan speed
minimum
vent opening
on conclusion of the cycle
The following table illustrates the factory settings of the timed
proving cycle.
SETTING
DEFAULT
MINIMUM...
MAXIMUM
work set-point
30 °C
20... 50 °C
humidification
80 %
40... 100 %
duration of the
phase
120 min
1... 300 min
fan speed
minimum
vent opening
on conclusion of the cycle
The following table illustrates the factory settings of the
environment cooling cycle; the opening and closing of the door
does not cause any consequence.
SETTING
DEFAULT
MINIMUM...
MAXIMUM
work set-point
50 °C
(param. r11)
0... 500 °C
fan speed
maximum, without inversion of
rotation direction (if envisioned)
vent opening
at the start of the cycle, for the
entire duration of the same