t4

0

1

- - -

0

enabling of the restriction between the injection of the steam

generated in direct mode and the fan

1 = YES - if the fan is off when the steam is injected, the

injection will be made on successive fan switch-on and if the

fan must switch-off during steam injection, it will be

switched-off on conclusion of the injection

t5

0

1

- - -

0

enabling of the restriction between the injection of the steam

generated in direct mode and the output for temperature regulation.

1 = YES - if the output is off when the steam is injected, the

injection will be made on successive output switch-on and if

the output must switch-off during steam injection, it will be

switched-off on conclusion of the injection

t6 t7 999 s 60

cycle time for injection of the steam generated with an external

humidifier

t7 0 t6 s 30

duration of the injection of the steam generated with external

humidifier corresponding to the maximum humidification

t8 0 999 s 60

injection delay of the steam generated with external humidifier from

start of a cooking cycle phase

t9

0

1

- - -

0

enabling of the restriction between the injection of the steam

generated with external humidifier and the fan

1 = YES - if the fan is off when the steam is injected, the

injection will be made on successive fan switch-on and if the

fan must switch-off during steam injection, it will be

switched-off on conclusion of the injection

t10

0

1

- - -

0

enabling of the restriction between the injection of the steam

generated with external humidifier and the output for temperature

regulation.

1 = YES - if the output is off when the steam is injected, the

injection will be made on successive output switch-on and if

the output must switch-off during steam injection, it will be

switched-off on conclusion of the injection

t11 0 240 s

5

delay of injection of the steam from output switch-on for the

regulation of the temperature or from fan switch-on

t12 0 999

°C/°F

(2)

120

temperature above which the injection of steam generated in direct

mode is activated and below which the injection of steam generated

with external humidifier is activated (referring to the temperature

detected by the environment probe; only if

t0 = 2)