EVCO EVCSR338J9 User Manual
Page 37

EVCO S.p.A.
Vcolor 338 S | Installer manual ver. 1.2 | Code 144VC338SE124
page 37 of 50
t4
0
1
- - -
0
enabling of the restriction between the injection of the steam
generated in direct mode and the fan
1 = YES - if the fan is off when the steam is injected, the
injection will be made on successive fan switch-on and if the
fan must switch-off during steam injection, it will be
switched-off on conclusion of the injection
t5
0
1
- - -
0
enabling of the restriction between the injection of the steam
generated in direct mode and the output for temperature regulation.
1 = YES - if the output is off when the steam is injected, the
injection will be made on successive output switch-on and if
the output must switch-off during steam injection, it will be
switched-off on conclusion of the injection
t6 t7 999 s 60
cycle time for injection of the steam generated with an external
humidifier
t7 0 t6 s 30
duration of the injection of the steam generated with external
humidifier corresponding to the maximum humidification
t8 0 999 s 60
injection delay of the steam generated with external humidifier from
start of a cooking cycle phase
t9
0
1
- - -
0
enabling of the restriction between the injection of the steam
generated with external humidifier and the fan
1 = YES - if the fan is off when the steam is injected, the
injection will be made on successive fan switch-on and if the
fan must switch-off during steam injection, it will be
switched-off on conclusion of the injection
t10
0
1
- - -
0
enabling of the restriction between the injection of the steam
generated with external humidifier and the output for temperature
regulation.
1 = YES - if the output is off when the steam is injected, the
injection will be made on successive output switch-on and if
the output must switch-off during steam injection, it will be
switched-off on conclusion of the injection
t11 0 240 s
5
delay of injection of the steam from output switch-on for the
regulation of the temperature or from fan switch-on
t12 0 999
°C/°F
(2)
120
temperature above which the injection of steam generated in direct
mode is activated and below which the injection of steam generated
with external humidifier is activated (referring to the temperature
detected by the environment probe; only if
t0 = 2)