EVCO EVCSR338J9 User Manual

Page 39

Advertising
background image

EVCO S.p.A.

Vcolor 338 S | Installer manual ver. 1.2 | Code 144VC338SE124

page 39 of 50

PARAM.

MIN.

MAX.

U.M.

DEF.

DIGITAL OUTPUTS

u0

0

1

- - -

0

type of vent output contact

0 = normally open (vent open with closed contact)

1 = normally closed (vent open with open contact)

u1

0

1

- - -

0

utility managed by the vent output

0 = ELECTROVALVE

ON/OFF

1 = MOTORISED

ELECTROVALVE - in this case the u2, u3 and u4

parameters will assume significance

u2 0 600

ds

(s/10)

120

duration of the inhibition of vent output from the conclusion of the

brief impulse for vent opening and from the conclusion of the long

impulse for vent closure (only if u1 = 1); see also u3 and u4

u3 0 600

ds

(s/10)

10

duration of the brief impulse for vent opening (only if u1 = 1); see

also u2 and u4

u4 0 600

ds

(s/10)

30

duration of the long impulse for vent closure (only if

u1 = 1); see also u2 and u3

PARAM.

MIN.

MAX.

U.M.

DEF.

SERIAL NETWORK

LA

1

247

- - -

247

device address

Lb

0

3

- - -

2

baud rate

0 = 2.400 baud

1 = 4.800 baud

2 = 9.600 baud

3 = 19.200 baud

LP

0

2

- - -

2

parity

0 = none (no parity)

1 = odd

2 = even

Notes

(1)

Properly set the parameters corresponding to the regulators after setting parameter P1

(2)

the unit of measurement depends on P1

(3)

if the duration of the power cur is shorter that the time established with parameter r12, when the power supply is restored,

the cycle will be re-proposed from the start of the phase during which the power cut occurred.