Interlogix Simon XT Installation Manual User Manual

Page 50

Advertising
background image

44

Simon XT Installation Manual

Function

Default Description

Supervisory tamper Off

Determines whether the panel sends supervisory reports to a
central station as a tamper (on), or a supervisory (off).

This option is typically used only in Europe where a supervisory
condition is required to report as a tamper.

No usage

Off

Determines whether the panel sends a No Usage report to the
central station if the user has not operated the system before the
programmed time expires (on), or not (off). The timer starts each
time the system is disarmed.

This is a customer service feature that alerts the central station if
a customer is not using their security system. The service provider
can then contact the customer to find out why the system is not
being used, and help correct any problems for the customer.

Swinger shutdown

On

Determines whether the panel prevents the same sensor from
activating an alarm more than once in a single period (on), or not
(off).

Swinger shutdown does not affect smoke and fire sensors.

Program report

Off

Determines whether the panel sends a report to the central station
anytime the programming mode is entered/exited (on), or not at all
(off). The panel sends a report whenever the dealer (Utility 1) or
installer (Utility 2) code is used to enter programming mode and
another report is sent when the programming session ends.

Fire verify

Off

If this option is off, the panel immediately reports to the central
station when a smoke detector goes into alarm.

With this option on, if a single smoke detector goes into alarm, the
panel will not report for 60 seconds unless another smoke
detector goes into alarm. If the first smoke detector is cleared of
alarm within the first 60 seconds, not report will be sent to the
central station unless it or a second smoke detector goes into
alarm within the panel siren timeout period (5 minutes).

Table 17: Communication modes

Function

Default

Description

Phone 1 report
mode

Off

Determines how the panel sends a report to the central
station for each of the phone numbers programmed.

The options are: All SIA, All CID, Alarm SIA, Alarm CID,
Nonalarm SIA, Nonalarm CID, backup SIA (phone failure
backup), Backup CID (phone failure backup), Voice dialer,
Off

Phone 2 report
mode

Off

Phone 3 report
mode

Off

Phone 4 report
mode

Off

Note: UL has only verified reporting compatibility with the CS5000 Digital Alarm Communicator
Receiver. For UL listed systems, Phone 1 Report Mode must be set to All SIA or All CID.

Alarms include: Fire, Intrusion, Emergency, Silent, and Alarm Cancels.