Vermont Castings Majestic Products NV360/580 Series

20003565

Remove glass door before service work

START

CHECK

Gas Supply On

Pilot Lights With Piezo
Ignitor

Lockout Has Engaged. Wait 60
Seconds And Try Again.

For Spark At Electrode While
Depressing Piezo
1/8" Gap To Pilot Hood Needed.

All Wiring Connections

Replace Piezo Ignitor

Supply Line Hooked Up

Shut off Valve Open

Pilot Stays Lit

For Air In The Lines

Thermopile Needs A Min.
325mv. Adjust Pilot Flame
Height.

All Wiring Connections

Replace Thermopile

Thermocouple Needs A Min. Of
14mv

Defective Valve. Turn To Pilot,
Meter Should Read Greater
Than 100mv. If Not, Replace.

Pilot Lights Main Burner

Valve Is Turned On

Wall Switch Is Not Turned On.
Watch For Grounded Wires!

Thermopile Needs A Min. 325mv.

Plugged Burner Orifice

System Ok

YES

NO

NO

NO

NO

YES

YES

YES