GROUND SCREW

(IN SPLICE BOX)

BLU

YEL

BLK

GROUND

LEAD

SINGLE-PHASE
CONNECTIONS
TO DISCONNECT
PER NEC

3-PHASE
CONNECTIONS

LEGEND
NEC – National Electrical Code

Field Wiring
Splice Connections

NOTE: Use copper wire only.

L1

L3

L2

C99057

Fig. 17 -- Line Power Connections

A05303

Fig. 18 -- Control Plate

The low--voltage circuit is fused by a board--mounted automotive

fuse placed in series with transformer SEC1 and R circuit. The C

circuit of transformer circuit is referenced to chassis ground through
a printed circuit run at SEC2 and metal control board mounting

eyelets. Check to be sure control board is mounted securely using
both factory--installed screws.

ACCESSORY INSTALLATION

A. Accessory Electric Heaters

Electric heaters may be installed in 50CR per instructions supplied
with electric heater package. See unit rating plate for

factory--approved electric heater kits.

NOTE: Units installed without electric heat should have a
factory--supplied sheet metal block--off plate installed over heater
opening. This reduces air leakage and formation of exterior
condensation.

B. Outdoor Air Thermistor (OAT)

A 2--screw terminal strip is provided for connection of an outdoor

temperature thermistor. This strip is marked OAT.

NOTE: While the installation of an outdoor temperature sensor
using the Infinity control board OAT terminals is optional, certain
Infinity features (ComfortHeat, electric heat lockout, auto humidity
control) will be lost.

OAT input is used to supply outdoor temperature data for system
level functions and for temperature display on User Interface.
Using two wires of field--supplied thermostat wire cable, wire one

lead of thermistor to one screw terminal and the other lead to
remaining screw terminal; there is no polarity to be observed. It is

strongly recommended that two wires be used to connect the
thermistor to eliminate noise interference in temperature reading. If

there are not two spare wires available in cable, one wire may be
used to connect thermistor to OAT screw terminal 1 and the other

lead of the thermistor can be wired to 24--vac COM (C) wire. OAT

screw terminal 1 is terminal located closest to the ABCD system
communications and is marked with a small number 1 next to the

terminal strip.

NOTE: Mis--wiring OAT inputs will not cause damage to either
Infinity control or thermistor. If the thermistor is wired incorrectly,
no reading will appear at User Interface. Re--wire thermistor
correctly for normal operation.

C. Humidifier Connections

The Infinity control board terminal marked HUM is provided for

low voltage (24--vac) control of a humidifier. No humidistat is
required as User Interface monitors indoor humidity. When

commanded to operate humidifier, the unit control will energize the

HUM output to turn humidifier on and de--energize HUM output to
turn humidifier off. Wire HUM and C terminals directly to

humidifier as shown in Fig. 14.
SPECIAL PROCEDURES FOR 208--V OPERATION
Be sure unit disconnect switch is open.
Disconnect the yellow primary lead from the transformer. See unit

wiring label. (See Fig. 15, 16 and 18)
Connect the yellow primary lead to the transformer terminal labeled
200--v.