HEAT PUMP WITH PURON

REFRIGERATION SECTION QUICK--REFERENCE GUIDE

Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement components are

designed to operate with Puron. Puron refrigerant cylinders are rose colored.

S

Puron refrigerant cylinders manufactured prior to March 1, 1999, have a dip tube that allows liquid to flow out of cylinder in
upright position. Cylinders manufactured March 1, 1999 and later DO NOT have a dip tube and MUST be positioned upside down

to allow liquid to flow.

S

Recovery cylinder service pressure rating must be 400 psig. DOT 4BA400 or DOT BW400.

S

Puron systems should be charged with liquid refrigerant. Use a commercial--type metering device in the manifold hose.

S

Manifold sets should be 750 psig high side and 200 psig low side with 520 psig low side retard.

S

Use hoses with 750 psig service pressure rating.

S

Leak detectors should be designed to detect HFC refrigerant.

S

Puron, as with other HFCs, is only compatible with POE oils.

S

Vacuum pumps will not remove moisture from oil.

S

Only use factory--specified liquid--line filter driers with rated working pressures no less than 600 psig.

S

Do not install a suction--line filter drier in liquid line.

S

POE oils absorb moisture rapidly. Do not expose oil to atmosphere.

S

POE oils may cause damage to certain plastics and roofing materials.

S

Wrap all filter driers and service valves with wet cloth when brazing.

S

A Puron liquid--line filter drier is required on every unit.

S

Do not use an R--22 TXV.

S

Never open system to atmosphere while it is under a vacuum.

S

When system must be opened for service, break vacuum with dry nitrogen and replace filter driers.

S

Do not vent Puron into the atmosphere.

S

Observe all warnings, cautions, and bold text.

S

Do not leave Puron suction line driers in place for more than 72 hrs.