Table 7—Troubleshooting Chart (Cont’d)

SYMPTOM

CAUSE

REMEDY

Head pressure too low

Low refrigerant charge

Check for leaks, repair and recharge

Restriction in liquid tube

Remove restriction

Excessive suction pressure

(Cool) High Heat load

Check for source and eliminate

Reversing valve hung up or leaking internally

Replace valve

Refrigerant overcharged

Recover excess refrigerant

Suction pressure too low

(Cool) Dirty air filter

Replace filter

(Heat) Outdoor coil frosted

Move timer on control board to 30 minutes between

defrost cycles

Low refrigerant charge

Check for leaks, repair and recharge

Metering device or low side restricted

Remove source of restriction

(Cool) Insufficient coil airflow

Increase air quantity

Check filter–replace if necessary

(Cool) Temperature too low in conditioned area

Reset UI setting

(Cool) Outdoor ambient below 55°F

Install low--ambient kit

Filter drier restricted

Replace

Compressor runs but outdoor fan does not

NC (normally closed) contacts on defrost board

open

Check condition of relay on board

Replace if necessary

IFM does not run

Blower wheel not secured to shaft

Properly tighten blower wheel to shaft

Insufficient voltage at motor

Determine cause and correct

Power connectors not properly sealed

Connectors should snap easily; do not force

IFM operation is intermittent

Water dripping into motor

Verify proper drip loops in connector wires

Connectors not firmly sealed

Gently pull wires individually to be sure they are

crimped into the housing