Table 7—

Troubleshooting Chart

SYMPTOM

CAUSE

REMEDY

Compressor and outdoor fan

will not start

Power failure

Call power company

Fuse blown or circuit breaker tripped

Replace fuse or reset circuit breaker

Defective contactor, transformer, control relay, defrost

board, or high--pressure, loss--

of--charge or low--pressure switch

Replace component

Insufficient line voltage

Determine cause and correct

Incorrect or faulty wiring

Check wiring diagram and rewire correctly

User Interface setting too low/too high

Reset UI setting

DO NOT bypass this compressor time

delay–wait for 5 minutes until time--delay

relay is de--energized

Units have a 5--minute time delay

Compressor will not start but condenser fan

runs

Faulty wiring or circuit

Loose connections in compressor

Check wiring and repair or replace

Compressor motor burned out, seized, or

Determine cause

internal overload open

Replace compressor

Defective run capacitor, overload, or PTC (positive

temperature coefficient) thermistor

Determine cause and replace

One leg of 3--phase power dead

Replace fuse or reset circuit breaker

Determine cause

Low input voltage (20 percent low)

Determine cause and correct

Three--phase scroll compressor (size 030--

Scroll compressor is rotating in the wrong direction

Correct the direction of rotation by reversing the

060 unit) has a low pressure differential

3--phase power leads to the unit

Compressor cycles (other than normally satis-

fying) cooling/heating calls

Refrigerant overcharge or undercharge

Recover refrigerant, evacuate system, and re-

charge to capacities shown on rating plate

Defective compressor

Replace and determine cause

Insufficient line voltage

Determine cause and correct

Blocked outdoor coil

Determine cause and correct

Defective run/start capacitor, overload or start relay

Determine cause and replace

Faulty outdoor fan motor or capacitor

Replace

Damaged reversing valve

Determine cause and correct

Restriction in refrigerant system

Locate restriction and remove

Compressor operates continuously

Dirty air filter

Replace filter

Unit undersized for load

Decrease load or increase unit size

UI temperature set too low/too high

Reset UI setting

Low refrigerant charge

Locate leak, repair, and recharge

Frosted coil with incorrect defrost operation

Check defrost time settings

Reset as necessary

Check defrost temperature switch

Replace as necessary

Air in system

Recover refrigerant, evacuate system, and re-

charge

Outdoor coil dirty or restricted

Clean coil or remove restriction

Excessive head pressure

Dirty air filter

Replace filter

Dirty indoor or outdoor coil

Clean coil

Refrigerant overcharged

Recover excess refrigerant

Air in system

Recover refrigerant, evacuate system, and re-

charge

(Heat) Indoor air restricted or recirculating

Determine cause and correct

Indoor or outdoor air restricted or air short--cycling

Determine cause and correct

(Continued next page)