Carrier 50CR User Manual

Page 22

Advertising
background image

22

CHECKING AND ADJUSTING REFRIGERANT CHARGE
The refrigerant system is fully charged with Puron (R--410A)

refrigerant and is tested and factory sealed.

NOTE: Adjustment of the refrigerant charge is not required unless
the unit is suspected of not having the proper R--410A charge. The
charging label and the tables shown refer to system temperatures and
pressures in cooling mode only. A refrigerant charging label is
attached to the outside of the service access door. If charge level is
suspect in heating mode, reclaim all refrigerant and charge to
informative plate amount. (This information may be obtained from
the physical data table also.) The charging label and the tables
shown refer to system temperatures and pressures in cooling mode
only. A refrigerant charging label is attached to the outside of the
service access door.

IMPORTANT: When evaluating the refrigerant charge, an
indicated adjustment to the specified factory charge must always be
very minimal. If a substantial adjustment is indicated, an abnormal
condition exists somewhere in the cooling system, such as
insufficient airflow across either coil or both coils.

REFRIGERANT CHARGE
The amount of refrigerant charge is listed on the unit rating plate

and/or the physical data table. Refer to the Refrigeration Service

Techniques Manual, Refrigerants Section.
NO CHARGE
Check for leak. Use standard evacuating techniques. After
evacuating system, weigh in the specified amount of refrigerant

(refer to system rating plate).
LOW CHARGE COOLING
Use Cooling Charging Chart (Fig. 22). Vary refrigerant until the

conditions of the chart are met. Note that charging charts are
different from type normally used. Charts are based on charging the

units to correct subcooling for the various operating conditions.

Accurate pressure gauge and temperature sensing devices are
required. Connect the pressure gauge to the service port on the

suction line. Mount the temperature sensing device on the suction
line and insulate it so that the outdoor ambient does not affect the

reading. Indoor air CFM must be within the normal operating range
of the unit.
TO USE COOLING CHARGING CHARTS
Take the liquid line temperature and read the manifold pressure
gauges. Refer to the chart to determine what the liquid line

temperature should be.

NOTE: If the problem causing the inaccurate readings is a
refrigerant leak, refer to Check for Refrigerant Leaks section.

INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS

NOTE: Be sure that all supply-- and return--air grilles are open, free
from obstructions, and adjusted properly.

Unit 50CR utilizes state of the art ECM (Electronic Computated

Motor) ID Blower Motors. See user interface instructions for

detailed information on adjusting airflow.
Step 5—Defrost Control
QUIET SHIFT
Quiet Shift is a field--selectable defrost mode, which will eliminate

occasional noise that could be heard at the start of defrost cycle and
restarting of heating cycle. It is selected by placing DIP switch 3 (on

defrost board) in ON position.

When Quiet Shift switch is placed in ON position, and a defrost is
initiated, the following sequence of operation will occur. Reversing

valve will energize, outdoor fan will turn off, compressor will turn
off for 30 sec and then turn back on to complete defrost. At the start

of heating after conclusion of defrost reversing valve will

de--energize, compressor will turn off for another 30 sec, and the
outdoor fan will stay off for 40 sec, before starting in the heating

mode.
DEFROST
The defrost control is a time/temperature control which includes a

field--selectable time period (DIP switch 1 and 2 on the board)
between defrost cycles of 30, 60, 90, or 120 minutes (factory set at

30 minutes).
To initiate a forced defrost, two options are available depending on

the status of the defrost thermostat.
If defrost thermostat is closed, speedup pins (J1) must be shorted by
placing a flat head screw driver in between for 5 sec and releasing,

to observe a complete defrost cycle. When the Quiet Shift switch is
selected, compressor will be turned off for two 30 sec intervals

during this complete defrost cycle, as explained previously. When
Quiet Shift switch is in factory default OFF position, a normal and

complete defrost cycle will be observed.
If defrost thermostat is in open position, and speedup pins are
shorted (with a flat head screw driver) for 5 sec and released, a short

defrost cycle will be observed (actual length is dependent upon the
selected Quiet Shift position). When Quiet Shift switch is in ON

position, the length of defrost is 1 minute (30 sec compressor off

period followed by 30 sec of defrost with compressor operation).
On return to heating operation, compressor will again turn off for an

additional 30 sec and the outdoor fan for 40 sec. When the Quiet
Shift is in OFF position, only a brief 30 sec cycle will be observed.
If it is desirable to observe a complete defrost in warmer weather, the

defrost thermostat must be closed as follows:

1. Turn off power to outdoor unit.
2. Disconnect outdoor fan motor lead from OF2 on control

board (See Fig. 23). Tape to prevent grounding.

3. Restart unit in heating mode, allowing frost to accumulate on

outdoor coil.

4. After a few minutes in heating mode, liquid--line

temperature should drop below closing point of defrost

thermostat (approximately 30°F).

NOTE: Unit will remain in defrost until defrost thermostat reopens
at approximately 80°F coil temperature at liquid line or remainder
of defrost cycle time.

5. Turn off power to outdoor and reconnect fan motor lead to

OF2 on control board after above forced defrost cycle.

NON--COMMUNICATING

EMERGENCY

COOLING

/

HEATING MODE
This mode of operation is provided only in the case where the UI has

failed or is otherwise unavailable. If communications cannot be

established with the UI, the Infinity control board will enable the
following thermostat input terminals to allow simple thermostatic

control of the 50CR unit:

a. Y & O for cooling

b. W for electric heat (if applicable)

c. Y for heat pump heat

The Infinity control will respond to cooling and heating demands
with the maximum safe airflow based on electric heat size (if

applicable) and unit capacity.

50C

R

Advertising