Cdv series direct vent gas fireplace, Termination clearances, General information assembling vent pipes – Vermont Casting 36CDVTRN User Manual

Page 11: Flex vent pipes

Advertising
background image

11

CDV Series Direct Vent Gas Fireplace

20010175

Outside Corner

Inside Corner

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

A =

Combustible

6"(152mm)
Noncombustible

2"(50mm)

B =

Combustible

6"(152mm)
Noncombustible

2"(50mm)

A

Balcony -

with no side wall

G =

Combustible &

Noncombustible

12"(305mm)

G

Balcony -

with perpendicular side wall

H = 24"(610mm)
J = 20"(508mm)

H

J

B

Recessed Location

C = Maximum depth of 48"

(1219mm) for recessed

location.

D = Minimum width for back wall

of a recessed location.

Combustible 38"(965mm)

Noncombustible 24"(610mm)
E = Clearance from corner in

recessed location.

Combustible 6"(152mm)

Noncombustible 2"(50mm)

C

D

C

E

V

V

Combustible &

Noncombustible

V

V

V

General Information Assembling Vent Pipes

Canadian Installations:
Venting system must be installed in accordance with the
current CSA-B149.1 installation code.
USA Installations:
The venting system must conform with local codes and/
or the current National Fuel Gas code ANSI Z223.1/
NFPA 54.
Only venting components manufactured by CFM Corpo-
ration can be used in Direct Vent systems.

Flex Vent Pipes

Before joining the flex vent pipe to the unit, apply a
bead of high temperature sealant* (provided) to the 4”
pipe exiting the fireplace. Secure flex vent pipe in place
with a hose clamp (provided).
*Be sure the flex pipe overlaps at least 1” (25 mm) onto
the collars of the fireplace and termination. If the ter-
mination has an internal bead, be sure to overlap and
secure 1” (25 mm) past the bead.

584-15

Fig. 8 Termination clearances.

* Be sure the vent is actually crushed before proceed-
ing. Apply a tug to be sure the vent will not slip off the
collars.
Repeat process with 7” flex vent pipe. The same proce-
dure must be performed on the vent side.

FP1471

flex vent

Hose Clamp

Apply High Tempera-

ture Sealant

FP1471a

Fig. 9 Apply high temperature sealant to 4” and 7” pipes.