Cdv series direct vent gas fireplace – Vermont Casting 36CDVTRN User Manual

Page 22

Advertising
background image

22

CDV Series Direct Vent Gas Fireplace

20010175

1

2

3

4

Example:

Elbow 1 = 90°

Elbow 2 = 45°

Elbow 3 = 45°

Elbow 4 = 90°

Total angular variation = 270°

1 + 2 + 3 + 4 = 270°

FP1239

Fig. 42 Maximum number of elbow degrees.

STEP 1
Locate vent opening on the wall. It may be necessary
to first position the fireplace and measure to obtain hole
location. Depending on whether the wall is combustible
or noncombustible, cut opening to size. (Fig. 43)
For combustible walls first frame in opening.
Combustible Walls: (Fig. 43) Cut a 9³⁄₈”H x 9³⁄₈”W (240
x 240 mm) hole through the exterior wall and frame as
shown.
Noncombustible Walls: (Fig. 43) Hole opening must
be 7¹⁄₂” (190 mm) in diameter.

Vertical Sidewall Installations

VO584-100

Vent Opening

2/99 djt

Vent Opening for Combustible Wall

9³⁄₈”

(240mm)

9³⁄₈”

(240mm)

Fireplace Hearth

Framing

Detail

Opening for Noncombustible Wall

7¹⁄₂”

(190mm)

VO584-100

Fig. 43 Locate vent opening on wall.

STEP 2
Place fireplace into position. (Fig. 44) Measure the verti-

cal height (X) required from the base of the flue collars

to the center of the wall opening.

X

FP1240

Fig. 44 Vertical height requirement.

STEP 3
Using appropriate venting component(s) attach to
fireplace with three (3) screws. (Fig. 45) Follow with the
installation of the inner and outer elbow. Again secure
joints with three (3) sheet metal screws.
STEP 4
Measure the horizontal length requirement including
a 2” (51 mm) overlap, ie from the elbow to the outside
wall face plus 2” (51 mm) (or the distance required if
installing a second 90° elbow). (Fig. 45)

Always install horizontal venting on a level
plane.

X

FP1241

Fig. 45 Horizontal length requirement.