Cdv series direct vent gas fireplace, Vertical through-the-roof installation – Vermont Casting 36CDVTRN User Manual

Page 19

Advertising
background image

19

CDV Series Direct Vent Gas Fireplace

20010175

Example: Maximum horizontal length
0 x 45° elbows = 10’ (3 m)
1 x 45° elbows = 8¹⁄₂’ (2.6 m)
2 x 45° elbows = 7’ (2.1 m)
3. A minimum of an 8’ vertical rise.
4. Two sets of 45° elbows offsets within these vertical

installations. From 0 to a maximum of 8’ (2.4 m) of
vent pipe can be used between elbows. (Fig. 33)

5. 7DVCS must be used to support offsets. (Fig. 33)

This application will require that you first determine
the roof pitch and use the appropriate 7DVSKV (A, B
or F). (Refer to Venting Components List, Page 27)

Vertical Through-the-Roof Installation

FP1021

Typical vertical

through the roof

application

3/26/00 djt

Max.

8’

(2.4 m)

45°

Max.

8’

(2.4 m)

45°

50’

(15 m)

Typical
Ceiling

Support

Application

Typical Roof

Support Ap-

plication

FP1021

Typical Offset Installation

Fig. 33 Typical vertical roof applications.

1. Locate your fireplace.
2. Plumb to center of the (4”) flue collar from ceiling

above and mark position.

3. Cut opening equal to 9³⁄₈” x 9³⁄₈” (240 x 240 mm).
4. Proceed to plumb for additional openings through

the roof. In all cases, the opening must provide a
minimum of 1 inch clearance to the vent pipe, i.e.,
the hole must be at least 9³⁄₈” x 9³⁄₈” (240 x 240 mm).

5. Place fireplace into position.
6. Place firestop(s) #7DVFS or Attic Insulation Shield

#7DVAIS into position and secure. (Fig. 34)

CFM100

Firestop-Vertical

09/20/00

11"

11"

Joist

Joist

Firestop Spacer

Nails (4)

Upper Floor

Attic Insulation
Shield

Ceiling
Installation

CFM100

Fig. 34 Place firestop spacer(s) and secure.

7. Install roof support (Fig. 35 & 36) and roof flashing

making sure upper flange is below the shingles. (Fig.
35)

8. Install appropriate pipe sections until the venting is

above the flashing. (Fig. 35)

If there is room above ceiling level,
firestop spacer must be installed on both
the bottom and the top side of the ceiling
joists. If an attic is above ceiling level a
7DVAIS (Attic Insulation Shield) must be
installed. (Fig. 34)

The enlarged ends of the vent section
always face downward. (Fig. 35)

TWL101a

Twist Lock Pipe

2/8/99 djt

3 #5 Sheet Metal

Screws per Joint

Storm Collar

TWL101a

Fig. 35 Roof flashing.

Sealant