Cdv series direct vent gas fireplace, Vertical sidewall applications – Vermont Casting 36CDVTRN User Manual

Page 21

Advertising
background image

21

CDV Series Direct Vent Gas Fireplace

20010175

FP1012

Top vent max run

1/25/00 djt

20' (6m)

7.5' (2.3m)

Pipe Straps

Every 3’ (914mm)

Firestop/Zero

Clearance Sleeve

Pipe

Straps Every

3’ (914mm)

FP1012

Fig. 39 Support straps for horizontal runs.

Since it is very important that the vent-
ing system maintain its balance between
the combustion air intake and the flue
gas exhaust, certain limitations as to vent
configurations apply and must be strictly
adhered to.

The vent graph showing the relationship between verti-
cal and horizontal side wall venting will help to deter-
mine the various dimensions allowable.

Minimum clearance between vent pipes and
combustible materials is one 1” (25 mm)
on top, bottom and sides unless otherwise

noted.

When the vent termination exits through foundations
less than 20” (508 mm) below siding outcrop, the vent
pipe must flush up with the siding.
It is always best to locate the fireplace in such a way
that minimizes the number of offsets and horizontal
vent length of vent pipe from the flue collar of the fire-
place to the face of the outer wall.

Vertical Sidewall Applications

Horizontal plane means no vertical rise exists on this
portion of the vent assembly.

The maximum number of 90° elbows per side wall
installations is three (3).

If a 90° elbow is fitted directly onto the fireplace
flange the maximum horizontal vent run before the
termination or a vertical rise is 36” (914 mm).

If a 90° elbow is used in the horizontal vent run
(level height maintained) the maximum horizontal
vent length is reduced by 36” (914 mm). This does
not apply if the 90° elbows are used to increase or
redirect a vertical rise.

Example: According to the chart the maximum

horizontal vent length in a system with a 7.5’ (2.3 m)
vertical rise is 20’ (6 m) and if a 90° is required in
the horizontal vent it must be reduced to 17’ (5.2 m).

In Figure 41, Dimension A plus B must not be

greater than 17’ (5.2 m).

3'

(914mm)

FP1237

horizontal plane

12/02

FP1237

Fig. 40 Maximum horizontal vent run.

7.5'

(2.3m)

A

B

A + B = 17' (5.2m) Max.

1 x 90° elbow in horizontal plane = 3’ (914mm)

FP1238

Fig. 41 Maximum vent run with elbows.

The maximum number of 45° elbows permitted per
side wall installation is two (2). These elbows can be
installed in either the vertical or horizontal run.

For each 45° elbow installed in the horizontal run,
the length of the horizontal run MUST be reduced by
18” (457 mm). This does not apply if the 45° elbows
are installed on the vertical part of the vent system.

The maximum number of elbow degrees in a system
is 270°. (Fig. 42)