Cdv series direct vent gas fireplace, Rear wall installation twist lock pipe – Vermont Casting 36CDVTRN User Manual

Page 13

Advertising
background image

13

CDV Series Direct Vent Gas Fireplace

20010175

Top View

Straight Venting

Fig. 12 Rear vent applications.

13"

(330 mm)

Max.

������
���������
���������
�����

FP1598

Rear Wall Installation

Twist Lock Pipe

STEP 1
Locate vent opening on the wall. To locate hole center
consult with appropriate fireplace dimensions, Page 4.
Frame as shown below.
Combustible Walls (Fig. 13): Cut a 9³⁄₈”H x 9³⁄₈” W
(240 x 240 mm) hole through the exterior wall and
frame as shown.
Noncombustible Walls (Fig. 13): Hole opening must
be 7¹⁄₂” (190 mm) in diameter.

VO584-100

Vent Opening

2/99 djt

Vent Opening for Combustible Wall

9³⁄₈”

(240 mm)

9³⁄₈”

(240 mm)

Fireplace Hearth

Framing

Detail

Opening for Noncombustible Wall

7¹⁄₂”

(190 mm)

VO584-100

Fig. 13 Locate vent opening on wall.

STEP 2
Install interior firestop as shown in Figure 14.
STEP 3
Remove telescoping collar from termination.
STEP 4
Bend tab on outer casing up and insert collar onto fire-
place collars. (Fig. 14)

������
��������
������

Firestop

FP1600

Fig. 14 Install firestop.

Bend Tab

FP1005

Side View Vent Termination

1/25/00 djt

22”

(559 mm)

CL

Finished

Wall

Secure with Screw

Vent Termination

Firestop

FP1005a

Fig. 15 Side view of final unit location.

STEP 5
Twist the termination collar so it locks onto fireplace col-
lars. Run screw through tab to keep collar from turning.
(Fig. 15)
STEP 6
Slide fireplace into position.
STEP 7
From the outside of the house, slide the termination
onto the collars.
STEP 8
Secure the termination to the house with the four (4)
screws provided.