5 keri systems proximity readers, 6 wiegand compatible devices, 7 input and output connections – Keri Systems SB-293 User Manual

Page 20

Advertising
background image

Technical Reference Manual – PXL-250 and SB-293

Keri Systems, Inc.

Page 20

P/N: 01836-004

Revision 5.5

4.5

Keri Systems Proximity Readers

six conductor, shielded, stranded, AWG 24 wire (such as Belden 9536 or a larger
gauge)

1

maximum cable lengths by wire gauge are defined in Table 2

4.6

Wiegand Compatible Devices

five, six, or seven conductor, shielded, stranded, wire (depending upon the type of
Wiegand device)

NOTE: A minimum gauge of AWG 24 is required for data transfer with a 500-foot
maximum run length per Wiegand specification. However, the wire gauge to use
should be determined by the current draw requirements of the Wiegand device and the
actual length of the cable run. A +5 VDC Wiegand device must have +5 VDC at the
device (long cable runs have a voltage drop across the length of the run due to the
resistance in the cable). To ensure +5 VDC is available at the device a larger gauge of
wire (having less resistance) or a separate power supply at the Wiegand device may be
required.

4.7

Input and Output Connections

two conductor, stranded, AWG 22 or a larger gauge

NOTE: The Lock Output relay may require a heavier gauge of wire depending upon
the current demands of the lock and the length of the lock wiring run.

NOTE: If plenum cable is required, please reference the Belden plenum equivalent to
the cables listed above.

1. The MS-4000 requires only four conductors as it does not have a beeper or LED.

Table 2: Maximum Cable Lengths by Wire Gauge for Keri Systems

Proximity Readers

Maximum Cable Length by Wire Gauge

Reader Type

100 ft

250 ft

500 ft

MS-3000

AWG 24

AWG 24

AWG 24

MS-4000

AWG 24

AWG 24

AWG 24

MS-5000

AWG 24

AWG 24

AWG 24

MS-7000

AWG 24

AWG 24

AWG 20

MS-9000

AWG 24

AWG 22

AWG 18