Page 55

9.9

TB-1 – RS-485 Controller Network Connection

All PXL-250 controllers communicate, controller-to-controller, through an RS-485
serial communication network. Up to 128 controllers can be attached to this network.
Refer to the RS-485 Networking section on page 28 for information regarding network
cable routing.

To provide the best operating conditions for the RS-485 communication network, the
PXL-250 controller automatically ties the network shield to earth ground at one point,
preventing ground loops.

Refer to Table 14 and Figure 9-13 on page 56 and make the following connections to
attach a network communication line.

NOTE: Do NOT connect earth ground to the network cable shield. The PXL-250
controller automatically connects earth ground to the shield at one point on the
network. This single connection minimizes the effects of ground loops that can affect
controller performance.

NOTE: Keri Systems has identified specific extended network configurations that can
be used to wire a controller network communication bus (subject to certain
limitations). These configurations include a "star" pattern network communication
bus, a spur cable length of up to 5,000 feet, and a total network cable length of up to
16,000 feet. Refer to Addendum 3, PXL-250 Network Wiring Application Note (P/N
01824-002), for detailed information on extended network configurations.

Table 14: RS-485 Network

Communication Connections

TB-1

Description

Pin 1

Tx/Rx Negative

Pin 2

Tx/Rx Positive

Pin 3 Network Cable Shield