2 create a new doors/gates property set – Keri Systems Doors NetXtreme User Manual

Page 29

Advertising
background image

Figure 23: Door Properties Setup

Keri Systems, Inc.

Doors NetXtreme

TM

Reference Manual

01945-100 Rev. 4.0

Page 27

9.1.2

Create a New Doors/Gates Property Set

If one of the standard property sets does not fill the required settings, a new property set will need to be
created.

1. Click

or highlight an existing property set and click

.

2. When changes have been made to a property set, asterisks appear in the “Modified” column and

will remain there until the changes have been applied to the system.

3. Rename the “Property Set Name” to something that will be easy to understand.
4. Scroll through the list and change the following fields as needed for the specific property set.

Door Type - Door types allow an operator to identify the type of door being used. There are two door
types.

Standard – a standard door (default setting)

Gate – an electric gate (such as a gate controlling a parking lot)

Auto Unlock/Lock Timezone - The unlock/lock time zone allows an operator to assign a time zone to
a door for the automatic unlocking and locking of that door based on the timezone.

Unlock Time - The door unlock time is the number of seconds the controller holds the door lock relay
in the unlocked position to allow entrance or exit. A timer with this unlock value begins counting once
the card is presented to the reader. When the timer ends or the door closes, whichever occurs first, the
door lock relay resets to the locked position; the default time is 5 seconds (the door lock also resets
when the door is opened if a door status switch is attached to the door and is wired to the controller).

NOTE: The door unlock time is not in addition to the door open time. The door unlock time begins when
a card is presented to the reader and ends when the time specified has expired or the door closes,
whichever occurs first.

Extended Unlock Time - Used in connection with access groups, it allows an extended number of
seconds the controller holds the door lock relay in the unlocked position to allow entrance or exit.

Open Time - The door open time is the number of seconds a door can be held open for entrance or exit
before the controller generates a door held alarm. The default time is 20 seconds.

NOTE: The door open time is not in addition to the door unlock time. The door open time begins when
the door is opened and ends when the time specified has expired.