Notice – LAARS IGI-180C-5(N,X) - Service Manual User Manual

Page 14

Advertising
background image

II - SPECIFICATIONS

(cont.)

VENTING TABLE

Venting Table – Examples of Maximum Venting Distances with Various Elbow Combinations

35 Ft. (10.7 m)

1

41 (12.5 m)

29 Ft. (8.8 m)

2

41 (12.5 m)

23 Ft. (7.0 m)

3

41 (12.5 m)

17 Ft. (5.2 m)

4

41 (12.5 m)

33.5 Ft. (10.2 m)

1

1

41 (12.5 m)

32 Ft. (9.8 m)

1

2

41 (12.5 m)

27.5 Ft. (8.4 m)

2

1

41 (12.5 m)

NOTICE

Each 90 degree elbow is equivalent to 6 feet in straight vent pipe length. Each 45 degree elbow is

equivalent to 1.5 feet (0.46 m) in straight pipe length. The total maximum equivalent vent pipe

distance cannot exceed 41 feet (12.5 m) for horizontal venting distance. The maximum vertical height

for through the roof venting cannot exceed 21 feet (6.4 m). A condensate collector must be used if

the venting system height is more than 5 feet (1.52 m) above the water heater.

14

Maximum Straight

Pipe Distance

Number of

90 degree elbows

Number of

45 degree elbows

Maximum Total

Equivalent Feet

(meters) of Vent Pipe