IGI – 9. Removal of the Gas Valve Assembly:

CAUTION

120 volt potential exposure. Isolate the appliance and

reconfirm power has been disconnected using a multi-

meter.

a.

Remove the burner manifold, refer to

IGI - 8 a,b,c.

b.

Remove the four (4) Phillips screws that hold

the gas connection and gas control valve in

place at the bottom of the unit. Pull the gas

connection down to disconnect it from the gas

valve assembly. Inspect o-ring for damage

and/or defects. Ensure o-ring is in place when

re-assembling this connection.

c.

Disconnect connectors from solenoids, note

which connector goes to each solenoid, alone

with the proper wire colors. Pull gas valve

assembly out of unit.

IGI – 10.

Removal of Heat Exchanger:

CAUTION

120 volt potential exposure. Isolate the appliance and

reconfirm power has been disconnected using a multi-

meter.

a.

Remove PCB unit, refer to IGI - 2 a.

b.

Remove the heat exchanger water connection

lines, refer to IGI - 3 a.

c.

Remove the three (3) Phillip screws securing

the gas manifold assembly to the gas control

valve.

d.

Remove the six (6) Phillip screws that secure

the heat exchanger assembly in place.

e.

Disconnect connectors B1, B5, B6, C1, C3,

F1and F8. These are the igniter, flame rod,

thermo-fuse, hot water inlet and outlet

thermistor, and the anti-freeze heater

connections.

f.

Pull the heat exchanger out of the heater.

g.

Transfer all components found on the old heat

exchanger over to the new exchanger.

52