IGI – 11. Removal of Thermal Fuse:

CAUTION

120 volt potential exposure. Isolate the appliance and

reconfirm power has been disconnected using a multi-

meter.

This process may involve removing the heat exchanger

if the thermo-fuse on the rear of the heat exchanger is

blown. (Service Procedure IGI - 10, see page 52)

a.

The unit has four thermal fuses, see picture

below for location.

b.

Disconnect and remove the thermal fuse.

Re-install new thermo fuse using the existing

thermo fuse clips. Reconfirm inlet and

manifold gas pressures are set to the proper

setting. Ensure unit matches gas type being

supplied to the heater.