LAARS HEATING SYSTEMS

INLET SETPOINT

This is the desired boiler inlet water

temperature.

OPER DIFFERNTL __F

This sets the desired operating temperature

differential.

MAN RESET TEMP ___F

Displays unit’s outlet water temperature.

LOW TEMP WARN ___F

With this setting, you will tell the controller to

alarm when the boiler’s inlet temperature goes below

the temperature selected.

To change a value, select it by hitting the enter

key while the value is displayed. The value will start

to flash. Use the arrow keys to change the value.

When the value you desire is shown, press the enter

key. The value will stop flashing, indicating that the

value has been set. The readout will go back to

Display #1 if left inactive on any display for longer

than thirty (30) seconds.

Display #5 - Boiler Pump

If this menu is selected the following display

will appear.

BOILER PUMP

This is to indicate to the controller whether a

pump has or has not been connected, and how the

user wants the pump controlled.

Use the arrow keys to scroll through the

information, it will appear as follows:

PUMP INSTALLED = YES/NO

This indicates whether or not a pump will be

controlled by the LLS.

RUN CONT/AUTO = AUTO/CONT

When put in constant mode, the pump will run

continuously, regardless of whether or not there is a

call for heat. When put in auto mode, the pump will

start when there is a call for heat, stop when the call

for heat is ended, and extended run time ends, and

will run whenever the outlet temperature sensed is

within 5°F of the outlet water temperature setting, to

avoid nuisance high limit trips.

EXTENDED RUN ___MIN

Extended run is the pump time delay. After a

call for heat is satisfied, if the unit is in auto pump

mode, the pump will keep running for the length of

time entered by the user.

EXERCISE PUMP = NO/YES

If this function is turned on, during long periods

with no boiler/heater use (such as a hydronic boiler

system in the summer), the LLS will run the pump to

minimize the possibility of the pumps seizing up.

EXERCISE FREQ _ DAYS

This tells the controller how often you want the

pump run, if the exercise feature is enabled.

FREEZE PROTECT = ___

If the freeze protection feature is enabled, the

unit’s pump will be energized when the controller

detects inlet water temperature below what the user

has entered. This will keep the water moving through

the boiler to minimize the possibility of freezing.

Note that this will not protect the boiler if there is a

loss of electrical power to the unit, or if a prolonged

period of freezing temperatures occurs.

FREEZE PROTECT @ __F

This is the temperature at which the user wants

the freeze protection option to turn on.

To change a value select it by hitting the enter

key, the value will start to flash. Use the arrow keys

to change the value, when finished hit the enter key,

the value will stop flashing. The readout will go back

to Display #1 if left inactive on any display for longer

than thirty (30) seconds.

Display #6 - DHW Settings

If this menu is selected the following display

will appear.

DHW SETTINGS

IMPORTANT NOTE: The DHW (Domestic

Hot Water) connection on the LLS is only for the

Laars DHW sensor. Standard tank aquastats

must be connected to the LLS field interlock.

These Domestic Hot Water settings are only used

if the Laars DHW sensor is controlling tank

temperature.

Use the arrow keys to scroll through the

information, it will appear as follows:

DHW OPERATION ON _ OFF _

This tells the LLS controller that the Laars

DHW sensor is being used

DHW SETPOINT ___F

This sets the domestic water temperature, and is

measured at the DHW sensor.