LAARS HEATING SYSTEMS

•

Main Gas Flame Status (if main burner flame

sensor is present)

•

Pump / Circulator Status for Boiler and DHW

Pumps

•

Fan Status

•

Boiler Staging Status

•

“Service Required” Indicators

SECTION 2.

Operation

2.1 Sequence of Operation

1.The main power switch is “ON”.

2.Space heating or domestic hot water “call for

heat” signal is initiated.

3.The status of the water temperature at the boiler

inlet is verified.

4.The status of the water temperature at the boiler

outlet is verified.

5.Auxiliary terminals are checked to make sure the

circuit is closed.

6.Boiler pump is energized (if controlled by the

LLS).

7.Vent damper is opened (if installed)

8.Vent damper proving switch is verified.

9.Venting fans are energized (if installed).

10.Controller verifies that power venter proving

switch has been made.

11.Controller verifies that the high gas pressure

switch has not tripped if unit is equipped with

switch.

12.Proper minimum gas pressure is verified if the

unit has low gas pressure switch.

13.If used on the unit, rollout switch, blocked vent

switch and fusible links are checked.

14.Differential pressure switches to verify proper

air flow through units are checked (if the unit

has such devices).

15.Flow switch is checked.

16.Adequate water level is verified through Laars

Low water cutoff (if equipped).

17.Controller performs a pre-flame sense check.

18.Ignition system is energized.

19.Controller performs a post flame sense check.

20.The main gas valve assembly is activated as

prescribed.

21.The main burner is ignited.

22.Call for heat is satisfied.

23.Main gas valve assembly is deactivated.

24.The pump is allowed to operate for a preset time,

after which is stops (if pump delay is activated).

25.Venting fan is allowed to post purge, after which

is stops (if programmed).

26.Vent damper stays open if post purge is

activated, after which time it closes.

SECTION 3.

Field Installed Connections

Connections that are made to the LLS controller

are described in this section. Sensors, field-supplied

switches, power venters, aquastats, etc. can be

connected directly to the LLS control. This section

describes the method of connection, as well as any

important information regarding connections (see

Figure 1). Many connections will require

programming/setup of the controller.

The LLS-1 has several operating parameters that

can be changed to ensure that the boiler operation best

meets the needs for your application.

Laars controls boiler water temperature at

inlet.

See Sections 5 and 6 for specifics about

programming options.

Field Interlock - T1

The field interlock connection is commonly

referred to as a T-T connection. This is for tank

aquastats and heating thermostats / end switches. The

boiler will not fire unless this connection is made.

WARNING

The Field Interlock connection is NOT for safety

switches that are used to prevent the boiler from

firing. For field-supplied safety switches, connect

directly through the boiler wiring or through the

auxillary switch connection on the LLS (J32). When

components are wired through the Field Interlock,

voltage to the main gas valves can be energized by

the DHW (domestic hot water) sensor, if used.

Contact the factory if you have any questions about

how to connect safety switches to the boiler or the

LLS.

Important Note About Tank Aquastats:

Standard tank aquastats must be connected to the

Field Interlock (T1), not the DHW Tank Temp (T3).

The aquastat will call for heat when the tank

temperature drops, as in a standard water heater setup.

DHW Tank Temp connection is for the Laars DHW

Sensor only. Do not enable or program parameters for

domestic water on the LLS when using a standard

tank aquastat, or the controller will “look for” the

Laars DHW Sensor.

Outside Air Temp - T2

Laars’ OAT (outside air temperature) Sensor is

connected here when outdoor reset is used in a heating

system. To ensure proper operation, only the Laars

OAT sensor should be used with the LLS.