LAARS HEATING SYSTEMS

Water Level Sensor - J9

This connection is for a Laars Low Water

Cutoff only. (Other low water cutoff devices must be

connected to Aux SW - J32.) This connection is

made at the factory on units that are ordered with the

Low Water Cutoff option or other options that

include a Low Water Cutoff and is made in the field

when being added after the unit is on site.

Draft Pressure Switch - T4

When a draft fan is installed, a draft pressure

switch must be connected to ensure that the fan is

operating before the boiler is allowed to fire. Some

boilers and water heaters have built-in fans, and this

connection will be made to the unit’s internal draft

switch. Remove factory-installed jumper when

connecting draft pressure switch.

Vent Damper Control - T5

Vent dampers for units that require them

(Mighty Therm HH & PH, 175-250) are equipped

with a harness that requires wiring to the LLS

through the Vent Damper Control connection. See

Figure 2. Remove factory installed jumper when

connecting vent damper.

High & Low Gas Pressure Switches - T6

Figure 3. High and Low Gas Pressure Switch

Connection.

Figure 2. LLS Vent Damper Connection.

On pump-mounted units, this connection is

made at the factory. To interlock a pump to the LLS

for non-pump-mounted units, with the addition of

Laars’ high voltage (110V) relay & wire harness, use

this connection. One end of the wire harness connects

to J20 and the other end connects to the relay. A

separate 110V source is then connected through the

relay to the pump. This connection will handle

pumps as large as 1hP, 110V, single phase. The LLS

can be programmed to post-purge the pump and

monitor current draw through the relay.

DHW Pump Control - J19

This feature works with the Laars DHW

sensor only. To interlock a domestic water pump

(the pump between the heater and the storage tank) to

the LLS, with the addition of Laars’ high voltage

(110V) relay, wire harness, and DHW sensor, use

this connection. One end of the wire harness connects

to J19 and the other end connects to the relay. The

Laars DHW sensor must be connected to T3. A

separate 110V source is then connected through the

relay to the pump. This connection will handle

pumps as large as 1hP, 110V, single phase. The LLS

can be programmed to post-purge the pump and

monitor current draw through the relay.

Aux Sw - J32

This connection is made at the factory if

additional switches are ordered with the unit. If not,

field-supplied safety switches can be connected here.

Safety switches that must prevent the boiler from

firing must be connected here, or in series with the

boiler wiring, and NOT through the Field-Interlock

connection.

Alarm Relay - J29

This is a normally open 24VAC relay

connection, and is not a dry contact. With this alarm

relay, the user will have a 24VAC source for building

automation system alarms, bells, buzzers, or any

other alarm device, 8VA maximum.

Draft Inducer Relay - J28

When a boiler or water heater has a built-in

draft fan, this connection will be made at the factory.

For field-supplied draft fans or power venters with

the addition of Laars’ relay, the user can make a

connection here which, upon a call for heat, will call

the fan to operate. The LLS can be programmed to

pre-purge and/or post-purge the fan. Important note:

When this connection is used, a draft pressure switch

must be installed at connection T4 to prove the fan is

operating before the unit fires.

Vent Damper Relay - J27

When a heater is built with high and low gas

pressure switches, this connection is made at the

factory. When adding gas pressure switches in the

field, wire them per Figure 3. Remove factory-

installed jumper when connecting gas pressure

switches.

Main Pump Control - J20