Laars Logic System

Page 9

Power Venter Option

Power Venter Installed

·

“no” default

·

“yes” optional

Pre-Purge Time

·

0 minute min

·

10 minute max

·

0 (no purge) default

Post-Purge Time

·

0 minute min

·

10 minute max

·

0 (no purge) default

Vent Damper Option

Vent Damper Installed

·

“no” default

·

“yes” optional

Post-Purge Time

·

0 minute min

·

10 minute max

·

0 (no purge) default

Gas Valve Staging

(For two-stage units only)

Differential Between Stage 1 & 2

·

2°F min

·

50°F max

·

10°F default

SECTION 6.

Programming

The LLS-1 has program menus that allow you

to obtain boiler operation information and allow you

to change many of the operating parameters if you

wish to do so.

The up and down arrow keys (the two rightmost

Display #1 - Default

During periods of inactivity the LLS-1 readout

will display:

LAARS LOGIC SYSTEM. In order to access one of

the twelve menus hit the enter key.

Display #2 - Main Menu Selection

Use the arrow keys to scroll through the

information, to select a menu hit the enter key while

it is displayed. The readout will go back to Display

#1 if left inactive on any display for longer than

thirty (30) seconds. The list appears in the following

order:

BOILER INFORMATION

BOILER SETTINGS

BOILER PUMP

DHW SETTINGS

OUTDOOR RESET

ALARM SETTINGS

POWER VENTER OPTION

VENT DAMPER OPTION

GAS VALVE STAGING

PERFORM SYSTEM CHECK

SENSOR VALUES

OPERATING SUMMARY

Display #3 - Boiler Information

If this menu is selected the following display

will appear:

BOILER INFORMATION

This is data for how the boiler was built and

how the LLS was programmed. This data is entered

into the LLS-1 at the factory and cannot be changed.

It displays the model & serial number, the LLS

program number, the date the unit was manufactured

and the fuel type. The readout will go back to

Display #1 if left inactive on any display for longer

than thirty (30) seconds.

Use the arrow keys to scroll through the

information, it will appear as follows:

MODEL # _________

SERIAL # _________

LLS VER. ________

MFR DATE mm/dd/yyyy

FUEL TYPE __________

Display #4 - Boiler Settings

If this menu is selected the following display

will appear:

BOILER SETTINGS

Use the arrow keys to scroll through the

information, it will appear as follows:

Figure 4. LLS Menu Buttons.

keys) scroll through the menu. The right and left

arrow keys move back to previous menus. The enter

key (on the left) is pushed to select, or enter a menu

or to change displayed information (see Figure 4).

There are fifteen (15) separate Display Groups,

they are as follows: