LAARS HEATING SYSTEMS

Boiler Settings

Inlet Water Temperature

·

110°F min

·

220°F max

·

140°F default models HH/PH

·

110°F default models VW/PW

Operating Differential

·

2°F min

·

30°F max

·

15°F default models HH/PH

·

5°F default models VW/PW

Outlet Water Temperature

·

110°F min

·

240°F max

·

200°F default models HH/PH

·

180°F default models VW/PW

Low Return Water Temperature (for alarm)

·

40°F min

·

240°F max

·

80° default

Boiler Pump Settings

Boiler Pump Installed

·

“yes” or “no”

·

“yes” default for PH/PW

·

“no” default for HH/VW

Run Constant, Auto

·

“auto” default

·

“constant” optional

Pump Extended Run Cycle (pump delay time)

·

0 minute min

·

10 minute max

·

5 minute default

Pump Exercise

·

“no” default

·

“yes” optional

Pump Exercise Frequency

·

1 day min

·

9 days max

·

7 days default

Freeze Protection

·

“on” default

·

“off” optional

Freeze Protection to operate at

·

33°F min

·

50°F max

·

35°F default

Domestic Hot Water (DHW) Settings

IMPORTANT NOTE: The DHW connection

on the LLS is only for the Laars DHW sensor.

Standard tank aquastats must be connected to the

LLS field interlock. These Domestic Hot Water

settings are only used if the Laars DHW sensor is

controlling tank temperature.

DHW Operation

·

“off” default

·

“on” optional

DHW Setpoint Temperature

·

110°F min

·

190°F max

·

110°F default

Operating Differential

·

2°F min

·

30°F max

·

5°F default

Outdoor Reset Settings

(Not applicable to models VW & PW)

NOTE: Outdoor Reset is accomplished with

Laars Outdoor Reset sensor. Other sensors may not

be compatible with the LLS control logic.

Outdoor Air Temperature Sensor Installed

·

“no” default

·

“yes” optional

Outdoor Reset

·

“off” default

·

“on” optional

Outdoor Reset Ratio (Boiler inlet temp set point

governs high end of curve)

·

min

·

5 max

·

default

Maximum permissible water temperature (will

override reset curve)

·

150°F min

·

220°F max

·

190°F default

Minimum permissible water temperature (will

override reset curve)

·

110°F min

·

150°F max

·

130°F default

Warm Weather Shutdown

·

“on” default

·

“off” optional

Warm Weather Shutdown Temp

·

40°F min

·

120°F max

·

60°F default

Alarm Settings

External Alarm

·

“on” default

·

“off” optional

Internal Alarm

·

“on” default

·

“off” optional