Page 5

Figure 1. Laars Logic System Connections.

DHW Tank Temp - T3

This connection is for a Laars DHW

(domestic hot water) Sensor only. (Standard tank

aquastats must be connected to T1, the Field Interlock

connection on the controller.) The Laars DHW sensor

is a thermistor, not a switch, and this connection reads

resistance. Use of this sensor allows the user to

program domestic water features that are not available

when using a standard tank aquastat.

WARNING

If DHW sensor is used, additional components that

are tied to the field interlock will NOT prevent the

unit from firing when the DHW sensor calls for heat.

For field-supplied safety switches that must keep the

boiler from firing, connect directly through the boiler

wiring or through the auxiliary switch connection on

the LLS (J32).