LAARS Modulating Controls M4 & M4-EXT

WIRING TO MODULATING MOTORS

WIRING TO 4-20MA MODULATING MOTORS (A TERMINALS 13, 14), (B TERMINALS 16, 17), ...
•

The M4 can be equipped to operate up to four 4-20 mA modulating motors.

•

The M4-Extension can be equipped to operate up to six 4-20 mA modulating motors.

•

The M4 and the M4-Extension sources 24VDC excitation voltage for the 4-20mA signal.

•

Wire the (-) from the modulating motor to the boiler terminal on the M4 marked (GND). That is for boiler A,
the modulating (-) terminal will be 13.

•

Wire the (+) from the modulating motor to the boiler terminal on the M4 marked (mA). That is for boiler A,
the modulating (-) terminal will be 14.

13

15

14

17

16

-

+

+

mA

GND

VLT

CUR / VLT

A

-

+

mA

GND

CUR / V

B

Boiler 4-20mA

Modulation Output

4-20mA

Burner

Motor

-

+

WIRING THE VOLTAGE MODULATING MOTORS (A TERMINALS 13, 15), (B TERMINALS 16, 18),...
•

The M4 Extension can be equipped to operate up to six 0-5V, 0-10V, 1-5V, or 2-10V modulating motors.

•

Wire the (GND) from the modulating motor to the boiler terminal on the M4 marked (GND). That is for boiler
D, the modulating (GND) terminal will be 22.

•

Wire the (V+) from the modulating motor to the boiler terminal on the M4 marked (VLT+). That is for boiler
D, the modulating (V+) terminal will be 23.

22

20

9

21

24

23

+

+

mA

D

VLT

-

+

+

mA

GND

VLT

+

mA

UR / VLT

C

CUR / VLT

D

Boiler Voltage

Modulation Output

Voltage

Burner

Motor

GND

V+

CONNECTING TO THE M4-EXTENSION PANELS

•

The M4 is equipped with a 6-pin phone socket to connect to extension panels.

•

The M4-Extension is equipped with two 6-pin phone sockets to connect to M4 and an additional M4-Extension panel.

•

Only 6-wire phone cable must be used for proper operation.

•

Connection cable is provided as part of the M4-Extension package.

•

Phone cables must be of a 6-wire with 6-pin terminals. Phone cables can extend up to 100'.

Connecting M4 to

Two M4-Extension

Panels using RS485

SYSTEM

A

B

C

D

Full Modulation Sequencing Control

1 2

RUN

PROGRAM

FOR ALL CIRCUITS

120VAC, 6A RESISTIVE

OUTPUT RATINGS:

1A PILOT DUTY, 15A TOTAL

115VAC 60Hz , 30VA MAX

INPUT RATINGS:

USE COPPER WIRE,

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3

4 5

6

7

8

9 10 11 12

13

15

14

17

16

18

22

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

CLASS 1 WIRE ONLY.

---

---

PROVE
/DHW

SHUTDOWN

/SETBACK

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

LISTED

99RA

CAUTION

: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required
to de-energize the equipment before servicing.

SYSTEM

A

B

C

D

1 2

RUN

PROGRAM

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3

4 5

6

7

8

9 10 11 12

13

15

14

17

16

18

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

+

mA

22

-

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

PROVE

/DHW

SHUTDOWN

/SETBACK

FOR ALL CIRCUITS

120VAC, 6A RESISTIVE

OUTPUT RATINGS:

1A PILOT DUTY, 15A TOTAL

115VAC 60Hz , 30VA MAX

INPUT RATINGS:

USE COPPER WIRE,
CLASS 1 WIRE ONLY.

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

LISTED

99RA

CAUTION

: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required
to de-energize the equipment before servicing.

M4

FULL MODULATION SEQUENCING

M4 Module

F

H

J

Power

CAUTION:

Risk of Electric Shock.

More than one disconnect switch may be required
to de-energize the equipment before servicing.

PWR

L N

1 2

E

3 4

F

5 6

G

7 8

H

9 10

I

11 12

EXTENSION

MODULE

RS-485

Ext A

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

Use Copper Conductors Only.

OUTPUT RATINGS:

120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

LISTED

99RA

C

US

E

G

I

Comm

Ext B

K

M

O

L

N

P

15

14

VLT

mA

CUR / VLT

18

17

16

VLT

mA

GND

CUR / VLT

21

20

19

VLT

mA

GND

CUR / VLT

24

23

22

VLT

mA

GND

CUR / VLT

J

11 12

K

M

O

L

N

P

E

F

G

H

K

M

L

N

13

GND

16

GND

19

GND

22

GND

27

26

VLT

mA

CUR / VLT

30

29

16

VLT

mA

GND

CUR / VLT

25

GND

28

GND

I

J

O

P

M4-Extension A

M4-Ext

FULL MODULATION SEQUENCING EXTENSION

F

H

J

Power

CAUTION:

Risk of Electric Shock.

More than one disconnect switch may be required
to de-energize the equipment before servicing.

PWR

L N

1 2

E

3 4

F

5 6

G

7 8

H

9 10

I

11 12

EXTENSION

MODULE

RS-485

Ext A

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

Use Copper Conductors Only.

OUTPUT RATINGS:

120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

LISTED

99RA

C

US

E

G

I

Comm

Ext B

K

M

O

L

N

P

15

14

VLT

mA

CUR / VLT

18

17

16

VLT

mA

GND

CUR / VLT

21

20

19

VLT

mA

GND

CUR / VLT

24

23

22

VLT

mA

GND

CUR / VLT

J

11 12

K

M

O

L

N

P

E

F

G

H

K

M

L

N

13

GND

16

GND

19

GND

22

GND

27

26

VLT

mA

CUR / VLT

30

29

16

VLT

mA

GND

CUR / VLT

25

GND

28

GND

I

J

O

P

M4-Extension B

M4-Ext

FULL MODULATION SEQUENCING EXTENSION