Connecting to the m4-extension panels, M4 module, M4-extension a – LAARS M4-Ext - Installation Manual User Manual

Page 11: M4-extension b, M4-ext

Advertising
background image

Page 11

LAARS Modulating Controls M4 & M4-EXT

WIRING TO MODULATING MOTORS

WIRING TO 4-20MA MODULATING MOTORS (A TERMINALS 13, 14), (B TERMINALS 16, 17), ...

The M4 can be equipped to operate up to four 4-20 mA modulating motors.

The M4-Extension can be equipped to operate up to six 4-20 mA modulating motors.

The M4 and the M4-Extension sources 24VDC excitation voltage for the 4-20mA signal.

Wire the (-) from the modulating motor to the boiler terminal on the M4 marked (GND). That is for boiler A,
the modulating (-) terminal will be 13.

Wire the (+) from the modulating motor to the boiler terminal on the M4 marked (mA). That is for boiler A,
the modulating (-) terminal will be 14.

13

15

14

17

16

-

+

+

mA

GND

VLT

CUR / VLT

A

-

+

mA

GND

CUR / V

B

Boiler 4-20mA

Modulation Output

4-20mA

Burner

Motor

-

+

WIRING THE VOLTAGE MODULATING MOTORS (A TERMINALS 13, 15), (B TERMINALS 16, 18),...

The M4 Extension can be equipped to operate up to six 0-5V, 0-10V, 1-5V, or 2-10V modulating motors.

Wire the (GND) from the modulating motor to the boiler terminal on the M4 marked (GND). That is for boiler
D, the modulating (GND) terminal will be 22.

Wire the (V+) from the modulating motor to the boiler terminal on the M4 marked (VLT+). That is for boiler
D, the modulating (V+) terminal will be 23.

22

20

9

21

24

23

+

+

mA

D

VLT

-

+

+

mA

GND

VLT

+

mA

UR / VLT

C

CUR / VLT

D

Boiler Voltage

Modulation Output

Voltage

Burner

Motor

GND

V+

CONNECTING TO THE M4-EXTENSION PANELS

The M4 is equipped with a 6-pin phone socket to connect to extension panels.

The M4-Extension is equipped with two 6-pin phone sockets to connect to M4 and an additional M4-Extension panel.

Only 6-wire phone cable must be used for proper operation.

Connection cable is provided as part of the M4-Extension package.

Phone cables must be of a 6-wire with 6-pin terminals. Phone cables can extend up to 100'.

Connecting M4 to

Two M4-Extension

Panels using RS485

SYSTEM

A

B

C

D

Full Modulation Sequencing Control

1 2

RUN

PROGRAM

FOR ALL CIRCUITS

120VAC, 6A RESISTIVE

OUTPUT RATINGS:

1A PILOT DUTY, 15A TOTAL

115VAC 60Hz , 30VA MAX

INPUT RATINGS:

USE COPPER WIRE,

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3

4 5

6

7

8

9 10 11 12

13

15

14

17

16

18

22

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

CLASS 1 WIRE ONLY.

---

---

PROVE
/DHW

SHUTDOWN

/SETBACK

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

LISTED

99RA

CAUTION

: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required
to de-energize the equipment before servicing.

SYSTEM

A

B

C

D

1 2

RUN

PROGRAM

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3

4 5

6

7

8

9 10 11 12

13

15

14

17

16

18

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

+

mA

22

-

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

PROVE

/DHW

SHUTDOWN

/SETBACK

FOR ALL CIRCUITS

120VAC, 6A RESISTIVE

OUTPUT RATINGS:

1A PILOT DUTY, 15A TOTAL

115VAC 60Hz , 30VA MAX

INPUT RATINGS:

USE COPPER WIRE,
CLASS 1 WIRE ONLY.

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

LISTED

99RA

CAUTION

: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required
to de-energize the equipment before servicing.

M4

FULL MODULATION SEQUENCING

M4 Module

F

H

J

Power

CAUTION:

Risk of Electric Shock.

More than one disconnect switch may be required
to de-energize the equipment before servicing.

PWR

L N

1 2

E

3 4

F

5 6

G

7 8

H

9 10

I

11 12

EXTENSION

MODULE

RS-485

Ext A

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

Use Copper Conductors Only.

OUTPUT RATINGS:

120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

LISTED

99RA

C

US

E

G

I

Comm

Ext B

K

M

O

L

N

P

15

14

VLT

mA

CUR / VLT

18

17

16

VLT

mA

GND

CUR / VLT

21

20

19

VLT

mA

GND

CUR / VLT

24

23

22

VLT

mA

GND

CUR / VLT

J

11 12

K

M

O

L

N

P

E

F

G

H

K

M

L

N

13

GND

16

GND

19

GND

22

GND

27

26

VLT

mA

CUR / VLT

30

29

16

VLT

mA

GND

CUR / VLT

25

GND

28

GND

I

J

O

P

M4-Extension A

M4-Ext

FULL MODULATION SEQUENCING EXTENSION

F

H

J

Power

CAUTION:

Risk of Electric Shock.

More than one disconnect switch may be required
to de-energize the equipment before servicing.

PWR

L N

1 2

E

3 4

F

5 6

G

7 8

H

9 10

I

11 12

EXTENSION

MODULE

RS-485

Ext A

INPUT RATINGS:

115VAC 60Hz, 12VA MAX

Use Copper Conductors Only.

OUTPUT RATINGS:

120VAC, 6A RESISTIVE
1A PILOT DUTY, 15A TOTAL
FOR ALL CIRCUITS

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

LISTED

99RA

C

US

E

G

I

Comm

Ext B

K

M

O

L

N

P

15

14

VLT

mA

CUR / VLT

18

17

16

VLT

mA

GND

CUR / VLT

21

20

19

VLT

mA

GND

CUR / VLT

24

23

22

VLT

mA

GND

CUR / VLT

J

11 12

K

M

O

L

N

P

E

F

G

H

K

M

L

N

13

GND

16

GND

19

GND

22

GND

27

26

VLT

mA

CUR / VLT

30

29

16

VLT

mA

GND

CUR / VLT

25

GND

28

GND

I

J

O

P

M4-Extension B

M4-Ext

FULL MODULATION SEQUENCING EXTENSION

Advertising
This manual is related to the following products: