LAARS Heating Systems

MAXIMUM WATER TEMP

Adjustable 90ºF - 240ºF

Default: 240ºF

Button: MENU/Set Point/Offset/..../Maximum Water Temperature

in Reset only

This is the highest temperature heating water the M4 will circulate through the heating
system. It is available in Reset mode only.

When using a radiation system, it should be set according to the tubing or floor
manufacturer’s specification.

The Maximum Temperature must be at least 20°F higher than the Minimum Temperature.

BACK

SAVE

--- MAXIMUM WATER TEMP ----

240

F

[]

SYSTEM SETTINGS

Button: MENU/<System Settings>
The Settings 1 and Settings 2 menus provide access to adjusting and fine-tuning the system for
enhanced comfort and more fuel savings. The M4 behaves differently based on the selected
Control Modes (see Startup Settings).

BACK

SELECT

---------- SETTINGS 1 ----------

Gain

+0

Lead Rotation

Time

Purge Delay

0.0min

Lag Delay

0min

<More Settings>

BACK

SELECT

---------- SETTINGS 2 ----------

Standby Time

10min

System Run-On

0min

Setback

0 F

Last Stage Hold

0 F

Set Time

12:03Pm

<Day/Night Schedules>

RUN

PROGRAM

RUN

PROGRAM

• Gain
• Lead

Rotation

• Purge

Delay

• Lag

Delay

• Standby

Time

• System

Run-On

• Setback

Last Stage Hold

• Day/Night

Schedules

CAUTION

To be able to change the M4 settings the Program/Run Switch must be set to
Program. The switch is located under the Enclosure Wiring Cover for security.
The Enclosure Wiring Cover can be securely closed using a lock.

GAIN

Adjustable -10 to +10

Default: 0

Button: MENU/<System Settings>/Gain

The Gain adjusts the aggressiveness of the M4 PID logic to control how much
modulation is changed when the system temperature is different from the Set Point.

A Gain of 0 is a good starting point for all systems.

If during normal load conditions, the system temperature tends to fluctuate significantly,
decrease the Gain by two numbers (for example, from 0 to -2). Wait for at least 15
minutes before evaluating how the change has affected the system.

If, during normal load conditions the system temperature tends to remain consistently
below the Set Point (or consistently above the Set Point), increase the Gain by two
numbers (for example, from 0 to 2). Wait for at least 15 minutes before evaluating how
the change has affected the system.

BACK

SAVE

---------------- GAIN --------------

+0

F

[

]

BACK

SAVE

-------- LEAD ROTATION -------

Manual

Time

Last-On

BACK

SAVE

---- MANUAL LEAD STAGE ----

A

B

C

D

E

BACK

SAVE

--- AUTO ROTATE PERIOD ---

24

hrs

[

]

LEAD BOILER ROTATION

Adjustable Manual, Time (1 hr to 60 Days), Last-On

Default: Time (24Hours)

Button: MENU/<System Settings>/Lead Rotation

The Lead Boiler is the first boiler brought on when output is required.

The Lead Boiler can be rotated automatically, manually or based on Last-On. The
automatic rotation is recommended.

The current Lead Boiler is shown in brackets on the main display.

Only Boilers which are set to Auto Mode can be Lead. Therefore, not all the Boilers may
be available when manually selecting a new Lead Boiler.