INSTALL THE SENSORS

HEATING SYSTEM SENSOR (HSS) INSTALLATION

LOCATING HSS

Put the Heating System sensor approximately 10' feet past the last boiler on
the common supply header but before any major takeoffs.

The sensor must be located where it sees the output of all the boiler stages.
If a boiler is piped so that the sensor does not see its output, the M4 will not
sequence the boilers correctly.

Only use a Standard Brass Tube sensor (HT #904015-00 or equivalent).

The sensor wires can be extended up to 500' using a shielded 2-conductor
cable (Belden #8760 or equivalent). Do not ground the shield at the sensor
but at the panel using one of the terminals marked with an “O”.

Do not run sensor wires in conduit with line voltage wiring.

IMMERSION HEATING SYSTEM SENSOR (HSS) INSTALLATION

Install a 3/8"ID 1/2"NPT immersion well (HT #350147-00 or equivalent).

Insert the sensor probe of the supplied sensor into the well.

STRAP-ON HEATING SYSTEM SENSOR (HSS) INSTALLATION

Strap the sensor to the pipe using metal clamps. Do not over tighten the
clamp.

Strap pipe insulation around the sensor and pipe.

Immersion Well

3/8" ID 1/2" NPT

Heating System

Sensor

Common Supply Pipe

Sensor Probe

Immersion Heating System Sensor

Shield

Common Supply Pipe

Sensor Probe

Strap-On Heating System Sensor

Shield

Pipe Insulation

CAUTION

If the HSS can not sense the correct
heating system water temperature being
supplied to the building, the M4 will not
provide comfortable heat levels. Be sure
the HSS is located on a main supply pipe
which can not easily be isolated from the
system.

OUTDOOR SENSOR INSTALLATION

Only use the LAARS sensor included with the unit.

Locate the sensor in the shade on the north side of the building. The sensor
should never be in direct sunlight.

Be sure the location is away from doors, windows, exhaust fans, vents, or
other possible heat sources.

The sensor should be mounted approximately 10' feet above ground level.

Mount the sensor clip base to the outside of the building. Insert the sensor in
the middle and snap close the clip on the sensor.

The sensor wires can be extended up to 500' using shielded 2-conductor
cable. Do not ground the shield at the sensor but at the panel using one of the
terminals marked with an “O”.

Do not run sensor wires in conduit with line voltage wiring.

WARNING

The M4 is an operating control only. All boilers must have all safety
and limit controls required by code. It is the responsibility of the
installer to verify that all the safety and limits are working properly
before the M4 is installed.

CAUTION

Determining the proper location for the Outdoor Sensor is very
important. The M4 will base the heat on the outdoor temperature
information it receives from this location. If the sensor is in the
sun, or covered with ice, its reading will be different from the actual
Outdoor temperature (OD).

   

   

  
   

  