LAARS M4-Ext - Installation Manual User Manual

Page 15

Advertising
background image

Page 15

LAARS Modulating Controls M4 & M4-EXT

SELECTING THE MODULATING MODE

Normal, Parallel

Default: Normal

Button: MENU/<System Startup>/..../Modulating Mode

Some boilers run more efficiently as their modulation increases. For these units, it is
more energy efficient to run one unit in high than several units at lower modulation. If
your units are of this type, select Normal. This is the recommended setting for typical
steel and cast iron boilers.

There are some units that run more efficiently at lower modulation. If it is more energy
efficient to run several units at lower modulation than one at high, select Parallel. This is
typically used on copper boilers, low mass boilers, or burners with high turndown ratios.

BACK

SAVE

------ MODULATION MODE ------

Normal

Parallel

BACK

SAVE

----- PROVE/DHW SHARING ----

Prove

DHW Without Priority

DHW With Priority

PROVE/DOMESTIC HOT WATER (DHW)

Prove, DHW Without Priority, DHW With Priority

Default: Prove

Button: MENU/<System Startup>/..../Prove-DHW Sharing

Input Terminals 29 and 30 can be used with either of the above features.

When Prove is selected, the M4 will not start any boiler stage unless Prove terminals are
connected.

Using those terminals to connect to an aquastat for a Domestic Hot Water call and selecting either of the DHW options will
raise the calculated water temperature to the lower of 200°F or Max Water Temperature.

Domestic hot water without priority allows the SYS relay, mostly controlling a primary system pump, to remain energized
during a domestic hot water call (aquastat call on terminals 29 and 30). In Summer or when outdoor temperature is above
Outdoor Cutoff, a DHW call will energize the SYS relay. After the DHW call termination, the SYS relay will continue to run
for the System Run-On period before turning off.

However, domestic hot water with priority de-energizes the SYS relay during a domestic hot water call (aquastat call on
terminals 29 and 30) for a period of one hour. If after the hour period the DHW call still exist, the SYS relay will energize and
the M4 will continue in the higher temperature setting until the domestic hot water call has terminated.

BACK

SAVE

--------- SETBACK MODE --------

Day/Night Schedules

External Signal

SETBACK MODE

Day/Night Schedules, External Signal

Default: Day/Night Schedules

Button: MENU/<System Startup>/..../Setback Mode

The M4 has two levels of heat, a normal/day and a setback/night. The Normal is good
for when buildings are occupied and people are active. The Setback/Night holds a lower
system temperature and is for when buildings are unoccupied or inactive.

The Day/Night Schedules provides the user with a Day Time setting for Normal operation and a Night Time setting for Setback.

The External Signal option switches the M4 to Setback mode when an external signal is received through the Setback terminals.
This allows the M4 to be managed by an external device or control to provide setback.

BACK

SAVE

---------- BOOST MODE ---------

30 Minutes

Disabled

BOOST MODE

30 Minutes, Disabled

Default: 30 Minutes

Button: MENU/<System Startup>/..../Boost Mode

If you do not want a Boost simply select Disabled from the Boost Menu.

Boost is only available if Day/Night Schedules is selected as a Setback option.

The morning Boost is designed to return the building to comfortable ambient temperatures after the cooler Night (Setback)
period. The M4 will accomplish this by running elevated water temperatures (will add Setback setting to calculated water
temperature) for 30 minutes before the start of the Day schedule setting. That is, if the normal day set point at a specific outdoor
was 145˚F and the Setback setting was 20˚F, the boost will raise the system calculated temperature to 165˚F for 30 minutes
before the start of the Day Schedule setting.

BACK

SAVE

--------- SENSOR FAULT --------

All Off

All On

SENSOR FAULT

All Off, All On

Default: All On

Button: MENU/<System Startup>/..../Sensor Fault
The Sensor Fault will determine the operating status of all output stages that are set to Auto
when a sensor reads Short or Open.

Advertising
This manual is related to the following products: