Caution, Page 13 laars modulating controls m4 & m4-ext – LAARS M4-Ext - Installation Manual User Manual

Page 13

Advertising
background image

Page 13

LAARS Modulating Controls M4 & M4-EXT

----------- SETTINGS ------------

Season

Winter

Set Point

70 F

<System Settings>

<Maintenance>

<Histories>

<System Startup>

BACK

SELECT

BACK

SAVE

---------------- GAIN --------------

+0

F

[

]

BACK

SELECT

---------- SETTINGS 1 ----------

Gain

+0

Lead Rotation

Time

Purge Delay

0.0min

Lag Delay

0min

<More Settings>

BACK

SELECT

---------- SETTINGS 2 ----------

Standby Time

10min

System Run-On

0min

Setback

0 F

Last Stage Hold

0 F

Set Time

12:03Pm

<Day/Night Schedules>

BACK

SELECT

--- DAY/NIGHT SCHEDULES ---

Set Time

**:**

Day Schedule

**:**

Night Schedule

**:**

BACK

SAVE

-------- LEAD ROTATION -------

Manual

Time

Last-On

BACK

SAVE

---- MANUAL LEAD STAGE ----

A

B

C

D

E

BACK

SAVE

--- AUTO ROTATE PERIOD ---

24

hrs

[

]

BACK

SAVE

--------- PURGE DELAY ---------

1.0

min

[

]

BACK

SAVE

----------- LAG DELAY -----------

0

min

[

]

SYSTEM SETTINGS1

SYSTEM SETTINGS2

BACK

SAVE

-------- STANDBY DELAY --------

10

min

[

]

BACK

SAVE

-------- SYSTEM RUN-ON --------

0

min

[

]

BACK

SAVE

-------------- SETBACK -----------

0

F

[

]

BACK

SAVE

------ LAST STAGE HOLD ------

0

F

[

]

BACK

SAVE

----- SET PRESENT TIME -----

11:**Pm

EXTERNAL

SETBACK

Schedule

BACK

SELECT

---------- MAINTENANCE ---------

System Trim

+0 F

Outdoor Trim

+0 F

Soft-Off Delay

45sec

<Output Trim>

<Configuration>

MAINTENANCE

BACK

SAVE

--- SYSTEM SENSOR TRIM ----

+0

F

[

]

BACK

SAVE

-- OUTDOOR SENSOR TRIM ----

+0

F

[

]

BACK

SAVE

------- SOFT-OFF DELAY --------

45

sec

[

]

BACK

SELECT

-------- STAGE A TRIM --------

Output Trim

+0.0

<Prev Stage>

<Next Stage>

BACK

SAVE

-------------- STAGE A -----------

OUTPUT TRIM

+0.0

[

]

BACK

EXIT

------ CONFIGURATION 2 ------

A=4-20ma

B=0-10v

C=0-5v

D=2-10v

BACK

NEXT

------ CONFIGURATION 1 ------

v1.00c

Reset F

Normal

Day/Night Schedules

All Off

CAUTION

To be able to change the M4
settings the Program/Run Switch
must be set to Program. The switch
is located under the Enclosure
Wiring Cover for security. The
Enclosure Wiring Cover can be
securely closed using a lock.