LAARS M4-Ext - Installation Manual User Manual

Page 23

Advertising
background image

Page 23

LAARS Modulating Controls M4 & M4-EXT

BACK

NEXT

------ CONFIGURATION 1 ------

v1.00c

Reset F

Normal

Day/Night Schedules

All Off

BACK

EXIT

------ CONFIGURATION 2 ------

A=4-20ma

B=0-10v

C=0-5v

D=2-10v

CONFIGURATION

Button: MENU/<Maintenance>/<Configuration>
•

This menu option provides a consolidated view of the Startup settings the M4 has been
set to.

•

Additional stage settings will be available by selecting the NEXT option.

DISPLAY

The M4 display layout provides a variety of information that
gives an immediate picture of the operation status. The display
shows four boilers at a time. The two middle buttons scrolls the
screen to view additional boilers. Moreover, all the information
is brightly displayed. It can be viewed in brightly or dimly lit
rooms.
•

The buttons' functionality changes based on the screen and
menu level your in. The buttons' functionality are displayed
on a dark background on the screen bottom line.

•

Horizontal arrows are to scroll through the available stages.

•

Vertical arrows are to scroll through the menu functions
when in menus or to change values of settings when in its
specific screen.

OD=

35

F

SYS=

98

F

Prepurge Delay:67

A

B

C

D

50%

15%

---

---

STAGE

MENU

   

   

     

    

    

  



DISPLAY BOILER MODULATION STATUS
The M4 boiler modulation status gives immediate access to each boiler status. The following list show all possible boiler status:
•

---

Boiler is off due to no call for heat.

•

97%

Boiler is modulating at the indicated percentage.

•

ON

Boiler Stage Mode is set to ON and boiler is firing at 100% (boiler is in bypass).

•

OFF

Boiler Stage Mode is set to OFF and boiler stage is unavailable or boiler does not exist.

•

m95%

Boiler Stage Mode is set to Manual and set to the specified percent.

•

C/E

Boiler on Extension panel is communicating back to the M4..

DISPLAY MESSAGES
The M4 normal display layout reserved the second line for message indications. The following is a list of the most common
Message Display Line information:
•

Summer

The control is set to Summer. No heat is active.

•

Shutdown Active

The Shutdown Terminals are Shorted. No boilers will be active.

•

Shutdown by EMS

The EMS is below 2mA or above 22mA

•

DHW Call (171˚F)

There is a DHW (Domestic Hot Water) call. The M4 will Raise system Set Point to the indicated
temperature. DHW increases calculated temperature to 200˚F or Max Water Temperature, whichever
is lower.

•

Purge Delay: 23

The current boiler is in purge cycle and the remaining purge time in seconds is 23.

•

Holding Until 150˚F

The Lead boiler is in Last Stage Hold. This example shows that the lead stage will turn off when
system temperature reaches 150˚F.

•

System Run-On: 46

The System relay is ON for the System Run-On Delay. This example shows that it will remain in
System Run-On for an additional 46 seconds before turning off.

•

Waiting for Prove

The System relay is ON and the prove terminals are open before the lead boiler relay can energize.

•

Prove Failure

After boilers have run for a while, Prove signal was opened. The boiler relays will de-energize.
However, the System relay will remain energized.