LAARS Modulating Controls M4 & M4-EXT

BACK

NEXT

------ CONFIGURATION 1 ------

v1.00c

Reset F

Normal

Day/Night Schedules

All Off

BACK

EXIT

------ CONFIGURATION 2 ------

A=4-20ma

B=0-10v

C=0-5v

D=2-10v

CONFIGURATION

Button: MENU/<Maintenance>/<Configuration>

This menu option provides a consolidated view of the Startup settings the M4 has been
set to.

Additional stage settings will be available by selecting the NEXT option.

DISPLAY

The M4 display layout provides a variety of information that
gives an immediate picture of the operation status. The display
shows four boilers at a time. The two middle buttons scrolls the
screen to view additional boilers. Moreover, all the information
is brightly displayed. It can be viewed in brightly or dimly lit
rooms.

The buttons' functionality changes based on the screen and
menu level your in. The buttons' functionality are displayed
on a dark background on the screen bottom line.

Horizontal arrows are to scroll through the available stages.

Vertical arrows are to scroll through the menu functions
when in menus or to change values of settings when in its
specific screen.

OD=

35

F

SYS=

98

F

Prepurge Delay:67

A

B

C

D

50%

15%

---

---

STAGE

MENU

   

   

     

    

    

  



DISPLAY BOILER MODULATION STATUS
The M4 boiler modulation status gives immediate access to each boiler status. The following list show all possible boiler status:

---

Boiler is off due to no call for heat.

97%

Boiler is modulating at the indicated percentage.

ON

Boiler Stage Mode is set to ON and boiler is firing at 100% (boiler is in bypass).

OFF

Boiler Stage Mode is set to OFF and boiler stage is unavailable or boiler does not exist.

m95%

Boiler Stage Mode is set to Manual and set to the specified percent.

C/E

Boiler on Extension panel is communicating back to the M4..

DISPLAY MESSAGES
The M4 normal display layout reserved the second line for message indications. The following is a list of the most common
Message Display Line information:

Summer

The control is set to Summer. No heat is active.

Shutdown Active

The Shutdown Terminals are Shorted. No boilers will be active.

Shutdown by EMS

The EMS is below 2mA or above 22mA

DHW Call (171˚F)

There is a DHW (Domestic Hot Water) call. The M4 will Raise system Set Point to the indicated
temperature. DHW increases calculated temperature to 200˚F or Max Water Temperature, whichever
is lower.

Purge Delay: 23

The current boiler is in purge cycle and the remaining purge time in seconds is 23.

Holding Until 150˚F

The Lead boiler is in Last Stage Hold. This example shows that the lead stage will turn off when
system temperature reaches 150˚F.

System Run-On: 46

The System relay is ON for the System Run-On Delay. This example shows that it will remain in
System Run-On for an additional 46 seconds before turning off.

Waiting for Prove

The System relay is ON and the prove terminals are open before the lead boiler relay can energize.

Prove Failure

After boilers have run for a while, Prove signal was opened. The boiler relays will de-energize.
However, the System relay will remain energized.