TROUBLESHOOT - NO HEAT

START

Does the control have

power?

Is the control in

SUMMER mode?

Turn control power

ON.

NO

YES

Select WINTER from

the Season menu.

YES

Is the SYSTEM

Relay AND any of the

Boiler Output Relay

lights ON?

NO

Check the wiring
from control to the
boilers and the
pump.
Check plumbing for
heat distribution.

YES

Does the

Output relays that are

ON have continuity?

YES

Contact Factory for

control troubleshoot.

NO

Is the control

display indicates a

SHUTDOWN or PROVE

status?

NO

Check SHUTDOWN or

PROVE signal source.

YES

Is any of the

System or Outdoor

Sensors Short or Open?

NO

Replace the faulty

sensor.

YES

Is the Outdoor

sensor reading above

the Outdoor Cutoff

setting?

NO

Either change the

Outdoor Cutoff setting

or wait for the

Outdoor temperature

to drop below that

setting.

YES

Is the SYSTEM Relay

light ON?

YES

The control is in DHW

Priority and is

providing all output to

domestic water.

NO

Check control heat
settings for proper

heating Reset Ratio or

Set Point.

NO