Caution – Reznor JT4BD Unit Installation Manual User Manual

Page 11

Advertising
background image

11

High Pressure Switch (HPS) - A high-pressure switch is
factory-installed and located in the compressor discharge
line internal to the outdoor unit. The switch is designed to

de-energize the system when very high pressures occur

during abnormal conditions. Under normal conditions, the
switch is closed. If the discharge pressure rises above

575 psig, then the switch will open and de-energize the

outdoor unit. The switch will close again once the liquid

pressure decreases to 460 psig. Please note that the
switch interrupts the thermostat inputs to the unit. When
the switch opens and then closes, there will be a 5 minute

short cycling delay before the outdoor unit will energize.

low Pressure Switch (lPS) - A low-pressure switch is
factory-installed in select models only. If provided, this
located in the suction line internal to the outdoor unit. The
switch is designed to protect the compressor from a loss
of charge. Under normal conditions, the switch is closed.
If the suction pressure falls below 5 psig, then the switch

will open and de-energize the outdoor unit. The switch

will close again once the suction pressure increases
above 20 psig. Please note that the switch interrupts the
thermostat inputs to the unit. When the switch opens and
then closes, there will be a 5 minute short cycling delay

before the outdoor unit will energize.

t4BD rEFrIgErant cHargIng cHartS - coolIng onlY

application notes on the use of charging charts

notES:

1. All pressures are listed psig and all temperatures in °F
2. Discharge temperatures GREATER than charted values

indicate an UNDERCHARGED system.

3. Discharge temperatures LESS than charted values

indicate an OVERCHARGED system.

this equipment’s cooling system contains refrigerant under high pressure. always use safe and
environmentally sound methods when handling refrigerant handling or servicing the unit. review the
factory literature and safety warnings prior to servicing.

• When repairing system leaks, always use a nitrogen (inert) gas to protect the refrigerant system and pressure

check the repair before re-charging. Always replace the filter-dryers when performing any repair to the refrigeration
system with one capable of acid removal. After completing the repairs, evacuate the system to 350 - 500 microns
and weigh in the refrigerant to the amount specified on the unit rating label.

• Charging charts are valid for a variety of indoor, return air conditions and are most influenced by the outdoor

ambient temperature, outdoor fan operation and the unit operating voltage. Before using these charts, make sure
the unit is in a stable operating mode. As shown in the charging charts (Figures 6 - 12, pages 14 - 17), the ideal
system sub-cooling can vary over the range of operation. Reference the charts to determine the ideal amount of

sub-cooling for a given liquid pressure. Units charged to other values will not perform at the rated unit efficiency

(EER) or rated Coefficient of Performance (COP) in heating mode.

• To inspect a systems operation using quality instruments, match the measured liquid temperature to the units

chart. The measured liquid pressure reading should be within 3% of the charts value for most installations.

• For systems that are operating with more than a 5% deviation, inspect the unit for the proper voltage and phase

balance and the refrigeration system for leaks.

• Units that are operating at less then 95% of the nominal voltage or with a 2% phase imbalance may see a more

significant deviation than the amount stated above.

Do not use the charts in systems that have a fan cycling under low-ambient control. Refer to the low-ambient
kit instructions for more information. (If applicable)

lEgEnD

Shaded boxes indicate flooded conditions.

Rated design values. The suction pressure

will be lower than design value if outdoor air
flow, entering dry bulb, or entering wet bulb
temperatures are lower than design.

• Inspect the outdoor coil at the beginning of each cooling

season. Remove any debris. Clean the outdoor coil
and louvers as necessary using a mild detergent and
water. Rinse thoroughly with water.

• Inspect the electrical connections for tightness at the

beginning of each heating and cooling season. Service
as necessary.

cautIon:

the unit should never be operated without a
filter in the return air system. replace disposable
filters with the same type and size.

• Do not add additional oil to motors unequipped with oil

tubes. The compressor is hermetically sealed at the

factory and does not require lubrication.

coMPonEnt FunctIonS

comfort alert

tM

Diagnostics - The Comfort Alert

diagnostics module troubleshoots heat pump and air
conditioning system failures and accurately detects the
cause of electrical and system related failures without
any sensors. A flashing LED indicator communicates the

ALERT code to quickly direct the technician to the root

cause of a problem.

Advertising