Heat pump installation general information, Before you install the heat pump, Locating the heat pump – Reznor JT4BD Unit Installation Manual User Manual

Page 3: Packaging removal, Ground level, Rooftop

Advertising
background image

3

HEat PuMP InStallatIon

general Information

Split system heat pumps are designed only for outdoor
rooftop or ground level installations. This unit has been
tested for capacity and efficiency in accordance with
AHRI Standards and will provide many years of safe
and dependable comfort, providing it is properly installed
and maintained. Abuse, improper use, and/or improper
maintenance can shorten the life of the appliance and

create unsafe hazards.

To achieve optimum performance and minimize equipment

failure, it is recommended that periodic maintenance be
performed on this unit. The ability to properly perform

maintenance on this equipment requires certain

mechanical skills and tools.

Before You Install the Heat Pump

The cooling load of the area to be conditioned must be

calculated and a system of the proper capacity selected.
It is recommended that the area to be conditioned be
completely insulated and vapor sealed.

Check the electrical supply and verify the power supply

is adequate for unit operation. The system must be wired

and provided with circuit protection in accordance with

local building codes. If there is any question concerning

the power supply, contact the local power company.

The indoor section (air handler, furnace, etc) should be

installed before routing the refrigerant tubing. Refer to
the indoor unit's installation instructions for installation
details.

All units are securely packed at the time of shipment and

upon arrival should be carefully inspected for damage

prior to installing the equipment at the job site. Verify

coil fins are straight. If necessary, comb fins to remove
flattened or bent fins. Claims for damage (apparent or
concealed) should be filed immediately with the carrier.

Please consult your dealer for maintenance information

and availability of maintenance contracts. Please read
all instructions before installing the unit.

locating the Heat Pump

• Survey the job site to determine the best location for

mounting the outdoor unit.

• Overhead obstructions (Figure 1), poorly ventilated

areas, and areas subject to accumulation of debris
should be avoided.

• Sufficient clearance for unobstructed airflow through the

outdoor coil must be maintained in order to achieve rated
performance. See Figure 1 for minimum clearances to
obstructions.

• Consideration should be given to availability of electric

power, service access, noise, and shade.

Packaging removal

To prevent damage to the tubing onnections, carefully

remove the carton and user’s manual from the equipment.

Discard the shipping carton.

ground level

Ground level installations must be located according to

local building codes or ordinances and these requirements:

• Clearances must be in accordance with those shown

in Figure 1.

• A suitable mounting pad must be provided and be

separate from the building foundation. The pad must
be level and strong enough to support the unit’s weight.
The slab height must be a minimum of 2” (5 cm) above

grade and with adequate drainage. See Figure 1.

rooftop

• The method of mounting should be designed so that it

does not overload roof structures or transmit noise to
the interior of the structure. The roof must be structurally
capable of handling the weight of the unit.

• Full perimeter support is required under the unit.

Support must be made of weather resistant materials
and installed prior to unit installation.

• The support must be built to raise the unit 6" above the

roof.

Figure 1. clearance requirements

2” Mounting Pad

48”

24" for

Service Access

12" or 18”

See Note

12" or 18”

See Note

DO NOT

OBSTRUCT

TOP OF UNIT

NOTE:

Units require full perimeter clearances.

Installer must maintain 18” between two units

or 12” between single unit and structure.

6” from Building

or Structure

Advertising