Liquid Temperature [F]
Liquid Pressure [psig]
Remove refrigerant when above curve
Add refrigerant when below curve
Figure 9. Charging Chart for T4BD-036 Series (3 Ton Units) - TXV Matches
250
275
300
325
350
375
400
425
450
475
500
525
550
75
80
85
90
95
100
105
110
115
120
125
130
Liquid Temperature [F]
Liquid Pressure [psig]
Remove refrigerant when above curve
Add refrigerant when below curve
Figure 10. Charging Chart for T4BD-042 Series (3.5 Ton Units) - TXV Matches