Reznor JT4BD Unit Installation Manual User Manual
Page 14
14
Suct.
Press.
outDoor tEMPEraturE (°F)
70
75
80
85
90
95
100
105
liq.
Press.
Dis.
temp.
liq.
Press.
Dis.
temp.
liq.
Press.
Dis.
temp.
liq.
Press.
Dis
temp.
liq.
Press.
Dis.
temp.
liq.
Press.
Dis.
temp.
liq.
Press.
Dis.
temp.
liq.
Press.
Dis.
temp.
117
248
145
119
249
150
272
148
121
250
155
273
153
295
152
123
252
158
274
158
296
156
318
155
125
254
162
275
162
297
161
319
159
341
159
127
277
166
299
165
320
164
342
163
364
163
129
300
169
322
168
344
167
365
166
387
166
131
323
172
345
171
367
170
389
170
410
170
133
325
176
346
175
368
174
390
173
412
173
135
348
179
370
178
392
177
414
176
137
371
183
393
181
415
180
139
394
186
416
185
141
417
189
143
table 9. charging table for t4BD-060 Series (5 ton units) - orifice Matches
250
275
300
325
350
375
400
425
450
475
500
525
550
75
80
85
90
95
100
105
110
115
120
125
130
Liquid Temperature [F]
Liquid Pressure [psig]
Remove refrigerant when above curve
Add refrigerant when below curve
Figure 6. Charging Chart for T4BD-018 Series (1.5 Ton Units) - TXV Matches