Horizontal to downflow conversion, Condensate drain, Electrical wiring – Reznor R6GI Unit Installation Manual User Manual

Page 10: Horizontal to downflow conversion condensate drain, Avertissement, Warning

Advertising
background image

10

Figure 5

Figure 4

• Electrical connections must be in compliance with

all applicable local codes and ordinances, and with
the current revision of the National Electric Code

(ANSI/NFPA 70).

• For Canadian installations the electrical connections

and grounding shall comply with the current Canadian
Electrical Code (CSA C22.1 and/or local codes).

IMPORTANT NOTE:

If replacing any of the original wires supplied with the

furnace, the replacement wire must be copper wiring

having the same guage, voltage, and temperature
rating.

Figure 5. Condensate Drain & Service Ports

ACCESSORY

ROOF CURB

Figure 4.

Roof Top Installation

Condensate

Drain

High Pressure

Low Pressure

AVERTISSEMENT:

RISQUE DE CHOC ÉLECTRIQUE,

D’INCENDIE OU D’EXPLOSION

Le non-respect des avertissements de sécurité
pourrait entraîner

un fonctionnement dangereux

de l’appareil, des blessures graves, la mort ou
des dommages matériels.

Un entretein incorrect pourrait entraîner un

fonctionnement dangereux de l’appareil, des

blessures graves, la mort ou des dommages
matériels

• Couper toute alimentation électrique au

générateur d’air chaud avant de prodéder

aux travaux d’entretein.

• Au moment de l’entretien des commandes,

étiquetez tous les fils avant de les

débrancher. S’assurer de les raccorder
correctement.

• S’assurer que l’appareil fonctionne

adéquatement aprés l’entretien.

WARNING:

ELECTRICAL SHOCK, FIRE OR

EXPLOSION HAZARD

Failure to follow safety warnings exactly could

result in serious injury or property damage.

Improper servicing could result in dangerous
operation, serious injury, death or property
damage.

• Before servicing, disconnect all electrical

power to furnace.

• When servicing controls, label all wires

prior to disconnecting. Reconnect wires
correctly.

• Verify proper operation after servicing.

ELECTRICAL WIRING

Horizontal to Downflow Conversion

The unit is shipped ready for horizontal duct connections.
If down flow ducts are required, the unit must be converted
following the steps below for both the supply and return
ducts.
1. Remove both horizontal duct caps.
2. Locate the duct cap inside the duct openings and remove

the screw holding it in place.

3. Lift the cap out of the unit. (Hint: The cap can be pushed

up from the bottom by reaching through the fork slot).

4. Cover the horizontal duct openings with the horizontal

duct caps removed earlier in step 1. The insulation will
be on the indoor side.

5. Fasten the cover with screws to seal.
6. Remove and discard the two wood supports beneath

the unit.

Condensate Drain

Condensate is removed from the unit through the 3/4”
female pipe fitting (

Figure 5

) located on the front side of

the unit. Install a 2 inch condensate trap in the drain line of
the same size and prime with water. When connecting rigid
drain line, hold the female fitting with a wrench to prevent
twisting. Do not over tighten! Refer to local codes and
restrictions for proper condensate disposal requirements.