on an outside wall or any other location where its
operation may be adversely affected by radiant heat from
fireplaces, sunlight, or lighting fixtures, and convective
heat from warm air registers or electrical appliances.
Refer to the thermostat manufacturer’s instruction sheet
for detailed mounting information.

Heat / Cool Thermostat

2-Stage Heat / 2-Stage Cool Thermostat (Recommended):

For highest efficiency a 2 Stage Heating/Cooling
thermostat is recommended for this unit. A 2 Stage Cool
thermostat is required for control of the special variable
speed compressor. A 2 Stage Heat thermostat will allow
the gas heat to operate at a more efficient low heat
condition until there is a demand for higher heat output
to the conditioned space.

Single Stage Heat / 2 Stage Cool Thermostat (Optional):

A 2 Stage Cool thermostat is required for control of the
special variable speed compressor. A single stage Heat
thermostat can be used in conjunction with the automatic
heat staging jumper on the ignition control board. The heat
staging function will automatically move the unit into high

heat operation at the time interval selected:

OFF = Low heat operation only and ON = 10 minute delay
from low to high heat mode. See

Figure 12 (page 30)

.

Connect the Red, Yellow, Green, Blue, White, and Brown
(optional) low voltage thermostat wires to terminals R,
Y1 (1st Stage Cool), G, Y2 (2nd Stage Cool), W1 (1st
Stage Heat), & W2 (2nd Stage Heat-optional) on both
the thermostat sub-base and unit low voltage terminal
board. The C terminal (Black wire), is the 24V common
wire required on some thermostat models. See

Figure 17

(page 34)

&

Figure 18 (page 35)

.

Checking Heat Anticipator Settings

• Add the current draw of the system components.

OR

• Measure the current flow on the thermostat

R-W circuit

after the circulating blower motor has started. Set the heat
anticipator according to the thermostat manufacturer’s
instructions for heat anticipator settings.

Cooling Configurations

This unit is designed to operate 5 stages of cooling
controlled by any standard 2-stage thermostat. The
connection between Y1 on the thermostat and Y1 on
the unit terminal strip energizes first stage cooling. The
connection bewteen Y2 on the thermostat and Y2 on the
unit terminal strip energizes second stage cooling. The
additional stages are controlled by run time and outdoor
temperature. See

Figure 6

.

Heating Configurations

This gas pack is factory configured for two stage gas
heating operation with a two stage heating thermostat.
Connect the low voltage thermostat White & Brown wires
to W1 & W2, between the unit low voltage terminal board
and thermostat sub-base. See

Figure 6

.

To operate with a single stage heat thermostat, only
connect the low voltage thermostat White wire between
W1 on the unit low voltage terminal board and thermostat
sub-base. Reposition the automatic heat staging jumper
located on the ignition control module from OFF to ON
to set a 10 minute time delay before the gas furnace will
automatically move to high heat operation.

Table 4. Thermostat Wire Gauge

THERMOSTAT

WIRE GAUGE

RECOMMENDED T-STAT WIRE

LENGTH (UNIT TO T-STAT)

2-WIRE

(HEATING)

5-WIRE

(HEATING/COOLING)

24

55

25

22

90

45

20

140

70

18

225

110

COPPER WIRE SIZE — AWG

(1% VOLTAGE DROP)

SUPPLY WIRE LENGTH-FEET

SUPPLY CIRCUIT

AMPACITY

200

150

100

50

6

8

10

14

15

4

6

8

12

20

4

6

8

10

25

4

4

6

10

30

3

4

6

8

35

3

4

6

8

40

2

3

4

6

45

2

3

4

6

50

2

3

4

6

55

1

2

3

4

60

Wire Size based on N.E.C. for 60° type copper conductors.

Table 3. Copper Wire Size

Figure 6. Two Stage Heating / Two Stage

Cooling Configuration

TERMINAL STRIP

THERMOSTAT

R

G

C

W2

W1

RED

YELLOW

GREEN

BLACK

BLUE

WHITE

NOTE:
For use with compatible thermostats only. Refer to the thermostat manual for
detailed installation and programming instructions.

C

L

R

W1

G

Y2

Y1

Y1

Y2

W2

BROWN

L

OPTIONAL - SEE NOTE

O

E

NOT USED

NOT USED

Blower (Auto or Continuous ON)

24VAC (Common)

Diagnostics

1

ST

Stage Heat

24VAC

2

ND

Stage Cool

To Blower Control Board (Optional)

1

ST

Stage Cool

2

ND

Stage Heat

DEHUM