Run to the unit, Figure 7, Table 5 – Reznor R6GI Unit Installation Manual User Manual

Page 16: Manifold pressure. see, For the correct manifold

Advertising
background image

16

Figure 7

Table 6

Table 5

Ground

Joint

Union

Dripleg

Shut-Off Valve

with 1/8 NPT

plugged tap

Burner
Assembly

Manifold

Some utilities

require Shut-Off

Valve to be

4 to 5 feet

above floor

Automatic Gas Valve

(with manual shut-off)

Figure 7. Typical Gas Hookup - Right Side Entry

Table 5.

Manifold Pressure Setting (in WC) for Natural Gas

NATURAL GAS

HEATING VALUE OF

800 TO 899 BTU/ CU.FT.

ALTITUDE ABOVE SEA LEVEL

ZERO TO 1,999

2,000 TO 4,999

5,000 TO 5,999

6,000 TO 7,999

8,000 TO 10,000

3.5

3.5

3.5

3.5

3.0

NATURAL GAS

HEATING VALUE OF

900 TO 999 BTU/ CU.FT.

ALTITUDE ABOVE SEA LEVEL

ZERO TO 1,999

2,000 TO 4,999

5,000 TO 5,999

6,000 TO 7,999

8,000 TO 10,000

3.5

3.5

3.5

3.2

2.8

NATURAL GAS

HEATING VALUE OF

1,000 TO 1,100 BTU/ CU.FT.

ALTITUDE ABOVE SEA LEVEL

zero to 1,999

2,000 to 4,999

5,000 to 5,999

6,000 to 7,999

8,000 to 10,000

3.5

3.5

3.0

2.8

2.5

LP HEATING VALUE

OF 2,500 BTU/FT.3

ALTITUDE ABOVE SEA LEVEL

ZERO TO

1,999

2,000 TO

2,999

3,000 TO

4,999

5,000 TO

5,999

6,000 TO

7,999

8,000 TO

10,000

MANIFOLD PRESSURE

10.0

8.5

8.5

10.0

9.0

8.5

ORIFICE SIZE

55

55

55

56

56

56

NOTE: Manifold pressure based on sea level LP heating value of 2,500 Btu/cu. ft.

3

Table 6.

Manifold Pressure Setting (in WC) & Orifice Size for LP Gas