After the gas piping to the unit is complete, all connections
must be tested for gas leaks. This includes pipe connections
at the main gas valve, emergency shutoff valve and
other gas connectors. A soap and water solution can be
applied on each joint or union using a small paintbrush.
If any bubbling is observed, the connection is not sealed
adequately and must be retightened. Repeat the tightening
and soap check process until bubbling ceases.

• If pressure testing the gas supply lines at pressures

greater than 1/2 psig (14 inches WC), the unit must

be disconnected from the gas supply piping system

to prevent damage to the gas valve.

• If the test pressure is less than or equal to 1/2 psig

(14 inches WC), the unit must be isolated from the

gas supply line by closing the manual shut-off valve.

High Altitude Conversion

Conversion of this unit must be performed by qualified
service personnel, using only approved parts. All
installations must be made in accordance with the National
Fuel Gas Code and/or local jurisdiction codes.

High altitude conversion can be field performed by a simple
adjustment of manifold pressure or a change of the orifices
(if necessary) depending on type of gas being utilized. The
changes required depend on the installation altitude and
the heating value of the gas (based on sea level) which
can be obtained from your local gas utility. The heating
value of gas at high altitude is always lower than the sea
level heating value. The heating values listed in

Table 5

&

Table 6, (page 16)

are based on sea level values.

WARNING:

The reduction of input rating necessary for high

altitude installation may only be accomplished

with factory supplied orifices. Do not attempt to

drill out orifices in the field. Improperly drilled

orifices may cause fire, explosion, carbon

monoxide poisoning, personal injury or death.

If installing this unit above 2,000 feet, the input rate must

be reduced 4% per 1,000 feet of altitude (Example: 12%

at 3,000 feet, 16% at 4,000 feet, etc). NOTE: Deration is
necessary to compensate for low atmospheric pressure
at high altitudes.

For altitudes between 5,000 and 10,000 feet above sea
level, the unit can be converted by adjusting the furnace
manifold pressure. See

Table 5

for the correct manifold

pressure settings when using natural gas.

LP/Propane Gas Conversion

WARNING:

This unit was equipped at the factory for use

with natural gas only. A special kit, supplied by

the manufacturer, is required to convert the unit

to operate on LP/propane gas. Failure to use the

proper conversion kit can cause fire, explosion,

property damage, carbon monoxide poisoning,

personal injury, or death.

MPORTANT NOTE:

When converting this low NOx unit from natural gas

to propane (LP) gas, it is necessary to remove the

NOx baffles.

Conversion of this equipment to LP/Propane gas must
be made by qualified service personnel, using approved
factory parts. Conversion to LP can be accomplished by
replacing the natural gas orifices with the appropriate LP/
Propane orifices and then adjusting the manifold pressure
(

page 18

). Conversion to LP/Propane (sea level and high

altitude) is detailed in the installation instructions provided
with the conversion kit.

Please follow the instructions

provided in each kit.

Approved conversion kits are:

• The United States LP/Propane Gas Sea Level and High

Altitude Conversion Kit is for LP/propane conversion in

the United States at altitudes between zero and 10,000
ft. above sea level.

• The Canadian LP/Propane Gas Sea Level and High

Altitude Conversion Kit is for LP/propane conversions

in Canada at altitudes between zero and 4,500 ft. above
sea level.

For installations between zero and 4,999 ft. above sea
level, a #55 drill size orifice should be used. Installations
5,000 ft. above sea level require a #56 drill size orifice.

Table 6, (page 16)

lists the correct orifice size to use

at different altitudes.

After changing the orifices, it is required that you measure
the gas input rate by clocking the gas meter and using
the local gas heating value. See Verifying & Adjusting the
Firing Rate section on

page 18

.

AVERTISSEMENT:

RISQUE D’INDENDIE OU D’EXPLOSION

Le non-respect des avertissements de sécurité
pourrait d’entraîner des blessures graves, la
mort ou des dommages matériels.

Ne jamais utiliser une flamme nue por

vérifier la présence des fuites de gaz. Pour la

vérification de tous les joints, utiliser plutôt une

solution savonneuse commerciale fabriquée

spécifiquement pur la détection des fuites de

gaz. Un incendie ou une explosion peut entraîner

des dommages matériels, des blessures ou la
mort.

Advertising